I-25
August 1999
76-100016-001
Intelligent Suppression Control/Fire Alarm System
PEGAsys
TITLE
Installation Wiring Diagram
Addressable Relay Output Device
(Obsolete)
DRAWING No.
06-234563-001
REVISION
BA
SHEET
1 of 1
PROTECTIVE COVERING
UL
LABEL
RD
BK
S
E
E
N
O
TE
S1&9
NOTES
1.
RED
AND
BLACK
WIIRES
ARE
NON-POLERIZED
POWER
INPUTS.
REFER
TO
RX/TX
(CA
T.
Number
30-402001-000
&
74-200005-001)
W
IRING
D
IAGRAM
FOR
CONNECTION
TO
SMAR
T
DETECT
OR
MUL
TIPLEX
TRUNK
CIRCUIT
AND
CIRCUIT
CHARACTERISTICS.
2.
RELA
Y
OUTPUTS
ARE
NOT
SUPER
VISED.
RA
TING:
2A,
30
VDC
(RESISTIVE)
.6A,
120
VAC
(RESISTIVE)
3.
MAXIMUM
CURRENT
REQUIREMENTS:
ST
ANDBY
:
325uA
4.
5.
TYPICAL
PULSE
RA
TE:
RELA
Y
RESET
(ST
ANDBY):
9
S
ECOND
S
RELA
Y
SET
:
2
S
ECONDS
TROUBLE
ST
ATE:
NO
LED
PULSING
6.
REFER
TO
SYSTEM
OPERA
TION
MANUAL
FOR
APPLICA
TION
OF
ADDRESSABLE
RELA
Y
OUTPUT
7.
MOUNTS
IN
4“
SQUARE
ELECTRICAL
B
OX.
8.
MUST
BE
INST
ALLED
IN
A
U
.L.
LISTED
GANG
BOX..
9.
WIRING
INFORMA
TION
SHOWN
FOR
70-408002-000
THRU
70-408003-000.
SMAR
T
DETECT
OR
PRODUCT
NO.
’S
70-40XXXX-XXX
AND
71-40XXXX-XXX
MA
Y
B
E
M
IXED
ON
THE
SAME
MUL
TIPLEX
TRUNK
CIRCUIT
,BUT
SHALL
NOT
EXCEED
255
TOT
AL
DEVICES
PER
CIRCUIT
,2
040
PER
SYSTEM.
CAUTION:
…
LED
(SEE
NOTE
5)
FIELD CONNECTION
N.C.
COM.
N.O.
BROWN
(N
/C
)
ORANGE
(COM
)
WHITE
(N
/O
)
SEE
NOTE
2