August 1999
76-100016-001
Intelligent Suppression Control/Fire Alarm System
PEGAsys
7-11
Device
50-FT spacing
70-FT Spacing
Thermal
135° - 155° F
135° - 145° F
f.
This prompt asks the user for the alarm level for the
detector(s) to be set. Key in the desired alarm level and
press the return key. After pressing return the display will
read:
LEVELS SET ON XX DETECTORS
g.
This message verifies that the desired sensitivity adjust-
ments were done on XX amount of detectors. The sensitiv-
ity of all specified detectors (depending on which type was
previously selected) will be set in the previous procedure.
7-15
ADDRESSABLE CONTACT INPUT DEVICE
INSTALLATION
The Addressable Contact Input Devices are designed to be in-
stalled in a North American 2-1/2 in. (64 mm) deep one-gang
box, or a standard 4 in. square box 1-1/2 (38 mm) deep with a
one-gang blank cover. The AI terminal block will accept #14,
#16, and #18 AWG wire (1.5, 1.0, and 0.75 mm
2
respectively)
with size #18 being a minimum requirement. Refer to the wiring
the diagram in Appendix I for specific connection information.
Also refer to Chapter 2, Paragraphs 2-8.6 and 2-8.7 for setting
addresses and other parameters. The installation must comply
with national and local electrical codes.
7-16
ADDRESSABLE RELAY OUTPUT DEVICE
INSTALLATION
The Addressable Contact Output Devices are designed to be
installed in a North American 2-1/2 in. (64 mm) deep one-gang
box, or a standard 4 in. square box 1-1/2 (38 mm) deep with a
one-gang blank cover. The AI terminal block will accept #14,
#16, and #18 AWG wire (1.5, 1.0, and 0.75 mm
2
respectively)
with size #18 being a minimum requirement. Refer to drawing
number 06-234563-001 located in Appendix I, for specific con-
nection information on both devices. Also, refer to Chapter 2,
Paragraphs 2-8.6 and 2-8.7 for setting addresses and other
parameters. The installation must comply with national and lo-
cal electrical codes.
NOTE:
All Non Power Limited wiring must be routed away from
Power Limited wiring by a minimum of 1/4", per NFPA
& UL requirements. For Power Limited Circuits use
Type FPL, FPLP, or FPLR cable per NEC Article 760.
7-17
INSTALLATION CHECKOUT
Before powering up the
PEGAsys
for the first time, ensure that
the following has been completed:
a.
Central Control Module (CCM), RX/TX Module and System
Power Supply are secured to the back of the enclosure.
b.
CCM is connected to the RX/TX Module, Display Assem-
bly, System Power Supply (I/O bus and 24 VDC), and Re-
mote RS-232 peripheral(s) if any.
c.
CCMs configuration jumpers configured correctly to insure
proper operation of the programmable (signal / release)
output (MP1).
d.
Optional Motherboard if installed, is connected to the CCM
(I/O bus) and System Power Supply (24 VDC).
e.
RX/TX Module is connected to the CCM (RJ-12) and sys-
tem power supply (24 VDC).
f.
Output Modules if used, are installed in the Motherboard,
addressed correctly, configured for appropriate mode of op-
eration and their external wiring is connected correctly.
g.
Perform the Power-Up procedure in Chapter 4, Paragraph
4-5.
h.
Refer to Chapter 2 for system operations and programming.
7-18
CONNECTION OF PERIPHERALS
The following paragraphs will describe how to connect a termi-
nal or personal computer and a printer.
7-18.1 Connecting a Terminal or Personal Computer
A UL Listed EDP terminal or computer can be connected to the
system’s RS-232 port. A 6-wire RJ-12 type modular phone jack
(PC port), located on the CCM, provides easy connection.
The terminal or computer connection cable must have a RJ-12
type modular phone plug that connects to the CCM (use P/N
74-100016-003, for a DB9 connector for laptops, or P/N 74-
100016-001 for a DB25 connector for personal computers). The
connector at the terminal end must be of the type required by
the terminal device. Route the connection cable to one of the
RS-232 modular plug into the jack until it snaps into place. The
terminal or computer must be located in the same room as the
Central Control Panel.
The parameters and connections for the RS-232 printer port
are as follows:
PARAMETERS
9600 Baud
8 Data Bits
1 Stop Bit
No Parity
NOTE:
These parameters are fixed and not adjustable.
PIN and FUNCTION
1
TX
2
Signal Ground
3
RTS
4
CTS
5
N/C
6
RX
7-18.2 Connecting a Printer
The RS-232 printer port of the CCM is a supervised connec-
tion. The installer must enable the printer port for operation.
The enabling or disabling of the printer port would be done by
accessing the 1st or 2nd level menu.