I-24
August 1999
76-100016-001
PEGAsys
Intelligent Suppression Control/Fire Alarm System
TITLE
Installation Wiring Diagram
Addressable Contact Input Device
NO/NC (Obsolete)
DRAWING No.
06-234563-003
REVISION
BB
SHEET
1 of 1
PROTECTIVE COVERING
GRA
Y
ORANGE
BROWN
WHITE
TO
CA
THODE
TO
ANODE
TO
REMOTE
LED
TO
REMOVE
CONT
ACT
DEVICE
N/O
EOL
BN
WH
EOL
SEE
NOTE
3
UL
LABEL
TYPICAL
CONFIGURA
TIONS
BK
RD
SEE
NOTE
1
N.O.
CONT
ACT
DEVICES
MANUAL
PULL
S
TA
TION
W
ATERFLOW
SEE
NOTE
3
EOL
EOL
NOTES
1.
RED
AND
BLACK
WIIRES
ARE
NON-POLERIZED
POWER
INPUTS.
REFER
TO
RX/TX
(CA
T.
NO.
30-402001-000)
WIRING
DIAGRAM
FOR
CONNECTION
TO
SMAR
T
DETECT
OR
MUL
TIPLEX
TRUNK
CIRCUIT
AND
CIRCUIT
CHARACTERISTICS.
2.
SUPER
VISED
LINE
FOR
REMOTE
CONT
ACT
DEVICE
CONNECTION.
CAUTION:
CONT
ACT
DEVICE
MUST
BE
IN
THE
SAME
ROOM
AS
ADDRESSABLE
CONT
ACT
INPUT
DEVICE,
WITH
ALL
W
IRING
ENCLOSED
IN
CONDUIT
,AND
A
MAXIMUM
LENGTH
O
F
150
FT
.
3.
EOL
RESIST
OR:
820
OHM
.5
W
AT
T
(FENW
AL
PA
R
T
NO.
06-129025-001)
4.
TO
REMOTE
LED
(FENW
AL
PA
R
T
NO.
70-410001-000)
OBSER
VE
POLARITY
:ORANGE
(ANODE),
GRA
Y
(CA
THODE)
CAUTION:
LED
MUST
B
E
IN
THE
SAME
ROOM
AS
ADDRESSABLE
CONT
ACT
INPUT
DEVICE,
W
ITH
ALL
WIRING
ENCLOSED
IN
CONDUIT
AND
A
MAXIMUM
LENGTH
50FT
..
LED
CIRCUIT
IS
NOT
SUPER
VISED.
5.
MAXIMUM
CURRENT
REQUIREMENTS
310uA
380uA
6.
SMAR
T
DETECT
OR
PRODUCT
NO.
’S
70-40XXXX-XXX
AND
71-40X
XXX-XXX
MA
Y
B
E
M
IXED
ON
THE
S
AME
MUL
TIPLEX
TRUNK
CIRCUIT
,BUT
SHALL
NOT
EXCEED
255
TOT
AL
DEVICES
PER
CIRCUIT
,2040
PER
SYSTEM.
7.
TYPICAL
PULES
RA
TE:
NORMAL:
9
SECONDS
ALARM:
2
SECONDS
TROUBLE:
NO
LED
PULSING
8.
REFER
TO
S
YSTEM
OPERA
TION
MANUAL
FOR
APPLICA
TION
OF
ADDRESSABLE
CONT
ACT
INPUT
DEVICE.
9.
WIRING
INFORMA
TION
SHOWN
FOR
70-407002-00X
THRU
70-407004-00X.
ST
ANDBY
ALARM
CA
T.
NO.
DESCRIPTION
-000
NORMALL
Y
OPEN
-001
NORMALL
Y
CLOSED
FOR
SUPER
VISOR
Y
USE
ONL
Y