![Key Automation 14A Instructions And Warnings For Installation And Use Download Page 29](http://html1.mh-extra.com/html/key-automation/14a/14a_instructions-and-warnings-for-installation-and-use_1960053029.webp)
29
EN
14
DEAD MAN
0 = off
1 = on (safety devices disabled)
0
0
1
15
GATE OPEN
INDICATOR
0 = deactivated
1 = gate open light ON/OFF
2 = gate open light proportional
0
0
2
16
MAINTENANCE
Service interval cycle threshold. When the gate is closed, the
flashing light flashes quickly without stopping.
0 = off
10
1
200
x 1000
cycles
17
MAINTENANCE FLASH
Enabling of continuous flashing when service is required (only
active with gate closed).
0 = off
1 = on
0
0
1
18
ELECTROLOCK
ACTIVATION
0 = off
Activated for from 1 to 20 seconds when the motors start to open
the gate
2
0
20
s
19
WATER HAMMERING
IN OPENING
From motor M1 closed
0 = off
Motor M1 activated for from 1 to 30 seconds in the closing
direction to ensure that the electric lock releases
0
0
30
s
20
WATER HAMMERING
IN CLOSING
From motor M1 closed
0 = off
Motor M1 activated for from 1 to 30 seconds in the closing
direction to ensure that the electric lock engages
0
0
30
s
21
MOTOR RELEASE AT
STOP
Motor release from closed limit switch. Useful for lightweight gates
0 = off
1 to 10 release levels (1 = minimum release, 10 = maximum
release)
0
0
10
22
START UP BOOST
High-speed motor start-up. Useful for heavy gates in winter
0 = off
1 = on
0
0
1
23
CLOSING DELAY M 1
Leaf 1 closing delay with gate open
0 = Off
1 = 1 to 180 Seconds On
0
0
180
s
24
ENCODER
1 = Off (use of virtual encoder)
2 = On (use of motor’s physical encoder)
1
1
2
25
ENCODER PULSES
1 to 10 pulses per revolution of the physical encoder (only with 24
set as “2”)
1
1
10
26
DEFAULT
Restoring the default values
0
0
1