PRE-INSTALLATION

Notes:

 

-

Products are connected end-to-end via the integrated connectors at each end of the product. 
Note that there is an “input” and “output” connector on each product and orientation is critical.  
A common mistake is installing the products backwards.  

 

-

50 ft (15.2 m) total cable run max from controller to last segment.

A typical run installation includes:

•  X96 controller 

•  4-conductor cable (16 AWG or 12 AWG [1.5 mm

2

 or 3.5 mm

2

]) (ex. QSH-CBLP-M-500)

•  10 in (0.3 m) to 15 ft (4.6 m) or 24 ft (7.3 m) LS0 linear fixtures

•  Adapters

•  Right angle covers

Input

Input

Input

Input

Output

Output

Output

Output

7 | 

LS0

 INSTALLATION GUIDE

P/N 3662562 Rev A
© 2021 Lutron Electronics Co., Inc. All rights reserved.

Summary of Contents for CM-LS0

Page 1: ...LS0 LOW VOLTAGE LINEAR Installation Guide Models CM LS0 HW LS0...

Page 2: ...xample System Connection 10 Troubleshooting 10 Warranty Tech Support 11 Risk of electric shock Use in dry or damp locations only Turn power OFF at circuit breaker or remove fuse Damage to this product...

Page 3: ...ntroller 15 ft 4 6 m 15 ft 4 6 m 24 ft 7 3 m Input Current 0 259 A ft 0 259 A ft 0 161 A ft Input Voltage 21 V 21 V 21 V Flexible Connector input and Straight Connector output Available in custom orde...

Page 4: ...A Adapter Type B Screws Mounting Bracket Right Angle End Covers Other System Components ordered separately X96 Ketra Controller 4 wire cable ex QSH CBLP M 500 4 LS0 INSTALLATION GUIDE P N 3662562 Rev...

Page 5: ...ire a dedicated enclosure Notes The X96 Ketra controller provides low voltage power and communication to the LS0 luminaires The X96 needs to be between the AC mains power source and the run of LS0 lin...

Page 6: ...parallel wiring installations are not supported 120 277 V 60 Hz Mains Supply DO NOT WIRE IN PARALLEL 120 277 V 60 Hz Mains Supply 6 LS0 INSTALLATION GUIDE P N 3662562 Rev A 2021 Lutron Electronics Co...

Page 7: ...products backwards 50 ft 15 2 m total cable run max from controller to last segment A typical run installation includes X96 controller 4 conductor cable 16 AWG or 12 AWG 1 5 mm2 or 3 5 mm2 ex QSH CBLP...

Page 8: ...nductor cable to length Since this a low voltage wire conduits are not required 4 Ensure that there are enough adapters to complete your wiring The X96 controller only comes with one adapter to connec...

Page 9: ...on the cables and connections STEP 4 Connect to Controller See 3662581 install guide on how to install the X96 controller 1 Connect your 4 conductor cable to the Type A adapter Ensure you are followin...

Page 10: ...tput and 24 ft 7 3 m for long run Verify power connections red and black on QSH CBL M 500 are wired correctly on the X96 controller and each luminaire adapter Magenta LS0 is installed backwards Discon...

Page 11: ...questions and technical support please contact 844 588 6445 ketrasupport lutron com Ketra is a trademark or registered trademark of Lutron Electronics Co Inc in the US and or other countries 11 LS0 I...

Page 12: ...6231 E Stassney Ln Bldg 13 Suite 400 Austin TX 78744 www ketra com 512 872 4349 P N 3662562 Rev A...

Reviews: