14
EB: (examine B)- Unit will transmit present preset B
value (i.e. b = 000XXXXX).
SL XXXXX: (set “Low”)- Sets “set low” at requested
value. (-9999 to 49999)
EL: (examine “Low”)- Unit will transmit present “set
low” value (i.e. l = 000XXXXX).
SH XXXXX: (set “High”)- Sets “set high” at re-
quested value. (-9999 to 49999)
EH: (examine “High”)- Unit will transmit present “set
high” value. (i.e. h = 000XXXXX)
SJ XXXXX: (set “low out”)- Sets “out low” at re-
quested value. Only available with ANALOG
OUT option. (-9999 to 49999)
EJ: (examine “low out”)- Unit will transmit present
“out low” value. (i.e. j = 000XXXXX)
SK XXXXX: (set “high out”)- Sets “out high” at
requested value. Only available with ANALOG
OUT option. (-9999 to 49999)
EK: (examine “high out”)- Unit will transmit present
“out high” value. (i.e. k = 000XXXXX)
SN XX.X: (set norm)- Sets “norm” at requested
value. Must be a 3-digit number with decimal.
EN: (examine norm)- Unit will transmit present
“norm” value (i.e. n = 000XX.X).
SE i 4-20,e 0-5, e 1-5 or e 0-10: (set input)- sets
input to one of the 4 available types. Enter type
exactly as it appears on the display.
EE: (examine input)- Unit will transmit input type
(i.e. e 0-10).
SG XXXXX: (set dur A or hys A)- Sets dur A or hys
A at requested value. (dur A when A is assigned
to total; hys A when A assigned to rate).
EG: (examine dur A or hys A)- Unit will transmit
present dur A or hys A value (i.e.g = 000XXXXX)
SI XXXXX: (set dur B or hys B)- Sets dur B or hys
B at requested value. (dur B when B is assigned
to total; hys B when B assigned to rate).
EI: (examine dur B or hys B)- Unit will transmit
present dur B or hys B value (i.e.I = 000XXXXX)
SM secs, mins or hours: (set time base)- Sets time
base to desired setting.
EM: (examine time base)- Unit will transmit present
time base (i.e. secs).
ST XXXX: (set baud)- Sets baud at desired rate
(9600, 2400, 1200 or 300).
ET: (examine baud)- Unit will transmit present baud
rate (i.e. 9600).
SW lc pg or lc all: (set lock type)- Sets lock type at
specified setting.
EW: (examine lock type)- unit will transmit present
lock type (i.e. lc pg).
SX linear or sqrt: (set meter type)- Sets meter input
for linear or squre root extraction. Only available
with square law option.
EX: (examine meter type)- Unit will transmit present
meter type (i.e. linear).
SY A tot or A rate: ( set A type)- Assigns control
output A to rate or total.
EY: (examine A type)- Unit will transmit present A
type (i.e. a tot).
SZ B tot or B rate: ( set B type)- Assigns control
output B to rate or total.
EZ: (examine B type)- Unit will transmit present B
type (i.e. a tot).
SO XXXXX: (set lock code)- Sets lock code at
requested value.
EO: (examine code)- Unit will transmit present code
(i.e. o=000XXXXX).
SF X: (set decimal location)- Sets decimal at re-
quested location (0 to 4).
EF: (examine decimal location)- Unit will transmit
the present decimal location (i.e. f = 0000000X).
L CRPVABLH: (list)- The list can consist of any
combination of the eight available options. Any
addresss with a "*" next to it can be listed