EB: (examine B)- Unit will transmit present preset B

value (i.e. b = 000XXXXX).

SL XXXXX: (set “Low”)- Sets “set low” at requested

value. (-9999 to 49999)

EL: (examine “Low”)- Unit will transmit present “set

low” value (i.e. l = 000XXXXX).

SH XXXXX: (set “High”)- Sets “set high” at re-

quested value. (-9999 to 49999)

EH: (examine “High”)- Unit will transmit present “set

high” value. (i.e. h = 000XXXXX)

SJ XXXXX: (set “low out”)- Sets “out low” at re-

quested value.  Only available with ANALOG
OUT option. (-9999 to 49999)

EJ: (examine “low out”)- Unit will transmit present

“out low” value. (i.e. j = 000XXXXX)

SK XXXXX: (set “high out”)- Sets “out high” at

requested value.  Only available with ANALOG
OUT option. (-9999 to 49999)

EK: (examine “high out”)- Unit will transmit present

“out high” value. (i.e. k = 000XXXXX)

SN XX.X: (set norm)- Sets “norm” at requested

value.  Must be a 3-digit number with decimal.

EN: (examine norm)- Unit will transmit present

“norm” value (i.e. n = 000XX.X).

SE i 4-20,e 0-5, e 1-5 or e 0-10: (set input)- sets

input to one of the 4 available types.  Enter type
exactly as it appears on the display.

EE: (examine input)- Unit will transmit input type

(i.e. e 0-10).

SG XXXXX: (set dur A or hys A)- Sets dur A or hys

A at requested value. (dur A when A is assigned
to total; hys A when A assigned to rate).

EG: (examine dur A or hys A)- Unit will transmit

present dur A or hys A value (i.e.g = 000XXXXX)

SI XXXXX: (set dur B or hys B)- Sets dur B or hys

B at requested value. (dur B when B is assigned
to total; hys B when B assigned to rate).

EI: (examine dur B or hys B)- Unit will transmit

present dur B or hys B value (i.e.I = 000XXXXX)

SM secs, mins or hours: (set time base)- Sets time

base to desired setting.

EM: (examine time base)- Unit will transmit present

time base (i.e. secs).

ST XXXX: (set baud)- Sets baud at desired rate

(9600, 2400, 1200 or 300).

ET: (examine baud)- Unit will transmit present baud

rate (i.e. 9600).

SW lc pg or lc all: (set lock type)- Sets lock type at

specified setting.

EW: (examine lock type)- unit will transmit present

lock type (i.e. lc pg).

SX linear or sqrt: (set meter type)- Sets meter input

for linear or squre root extraction.  Only available
with square law option.

EX: (examine meter type)- Unit will transmit present

meter type (i.e. linear).

SY A tot or A rate: ( set A type)- Assigns control

output A to rate or total.

EY: (examine A type)- Unit will transmit present A

type (i.e. a tot).

SZ B tot or B rate: ( set B type)- Assigns control

output B to rate or total.

EZ: (examine B type)- Unit will transmit present B

type (i.e. a tot).

SO XXXXX: (set lock code)- Sets lock code at

requested value.

EO: (examine code)- Unit will transmit present code

(i.e. o=000XXXXX).

SF X: (set decimal location)- Sets decimal at re-

quested location (0 to 4).

EF: (examine decimal location)- Unit will transmit

the present decimal location (i.e. f = 0000000X).

L CRPVABLH: (list)- The list can consist of any

combination of the eight available options.  Any
addresss with a "*" next to it can be listed

Summary of Contents for INTELLECT-69PM2

Page 1: ...MONITOR INSTALLATION OPERATING INSTRUCTIONS MODELS INT 69PM2 99319 12 19 00 KESSLER ELLIS PRODUCTS CO 10 Industrial Way East Eatontown NJ 07724 Telephone 732 935 1320 Toll Free 800 631 2165 Fax 732 93...

Page 2: ...nternal circuit boards or devices Handling Procedure 1 Power to unit must be removed 2 Personnel must be grounded via wrist strap or other safe suitable means before any printed circuit board or other...

Page 3: ...ON SPECIFICATIONS 2 MOUNTING 3 WIRING 4 DEFINITIONS 5 FRONT PANEL OPERATIONS 7 PROGRAMMING FLOWCHART 7 PROGRAMMING 8 SETTING PRESETS PANEL LOCK 11 RS232 RS422 OPERATIONS 12 RS232 RS422 WIRING 16 TROUB...

Page 4: ...THIS PAGE IS BLANK...

Page 5: ...nal line fuse is recommended Add or replace the external fuse with the following specified type and rating only Input Power Recommended Fuse 115 VAC 100 mA slow blow fuse 230 VAC 50 mA slow blow fuse...

Page 6: ...0mA in ON state Input Linear 4 20mA 0 5V 0 10V or 1 5V selectable from the front panel Input Impedance Current 100 Voltage 115K Calibration The unit does all of the calibrations internally There are n...

Page 7: ...through the rubber gasket Insert the unit into the panel Slide the brackets up the groove to press against the back of the panel as shown in FIG A Insert the screws into the rear of the brackets Tight...

Page 8: ...ires are not run into the unit in a bundle with power input lines We recommend using shielded cable Con nect the shield to DC ground of the unit and earth at one point in the circuit preferably at the...

Page 9: ...he lockout will lock the program as well as the Presets and reset button The presets can be viewed but not changed LC PG LOCK PROGRAM When this is selected the lockout will lock only the program The R...

Page 10: ...t list the unit will transmit the present peak value when the strobe is acti vated UALLEY VALLEY When this is added to the print list the unit will transmit the present valley value when the strobe is...

Page 11: ...h PRO GRAM choices Press to step through set up choices in program mode iNPUT i 4 20 E 0 5 E 1 5 E 0 10 RUN MODE RELAYS HYS A HYS B XXXXX RUN MODE LOC LC ALL LC PG CODE RUN MODE SETUP DECLOC SET LO SE...

Page 12: ...xisting HyS A value XXXXX HYS B PRGM PRGM ENTER This section of the menu sets up the open collector outputs and or relays Hys hysteresis The number of units below the preset that the output will remai...

Page 13: ...e value press the A button until the digit passes 4 a nega tive sign will appear SET HI Display value for the highest input 5 or 10V 20mA i e 20mA 100 Key in the desired high value and press RST ENTER...

Page 14: ...ID number This ID number 1 to 99 must be addressed to bring the unit on line If the unit number is set at 00 the unit cannot be addressed Key in the desired unit number and press RST ENTER to enter d...

Page 15: ...ayed value is not the desired preset press the key s under the digit to be changed To enter a negative value press the A button until the digit passes 4 a negative sign will appear Key in the lock cod...

Page 16: ...2400 or 9600 are available Select the desired baud rate from the menu see step 5 of the programming section PRINT LIST The serial interface card is equipped with a strobe line When the strobe line is...

Page 17: ...A Type Z B Type O Code F Decimal POSSIBLE COMMANDS Each command must be followed by a carriage return for execution DXX device unit ID Unit XX will come on line and stay on line until another device...

Page 18: ...set dur B or hys B Sets dur B or hys B at requested value dur B when B is assigned to total hys B when B assigned to rate EI examine dur B or hys B Unit will transmit present dur B or hys B value i e...

Page 19: ...t data before the return enter is sent Once a return enter is sent the unit begins processing the data and will transmit the requested data on a non priority basis over the data transmit line The unit...

Page 20: ...ould be made as follows DB 9 CONNECTOR COMPUTER Transmit data pin 2 Receive data Receive data pin 3 Transmit data Ground pin 5 Ground PRINTER HOOKUP When connecting the unit to a printer you must firs...

Page 21: ...ncorrect 2 High and low scaling set tings are incorrect 3 Transmitting device is de fective 4 Unit is defective 1 Input wiring is incorrect 1 Recheck power wiring 1 Use a different power sup ply or in...

Page 22: ...ur warranty repair modification or returned goods process please contact your local distributor WARRANTY This product is warrantied against defects in materials and workmanship for a period of two 2 y...

Reviews: