![Kessel Comfort PLUS Original Operation Manual Download Page 53](http://html.mh-extra.com/html/kessel/comfort-plus/comfort-plus_original-operation-manual_1957849053.webp)
Installation and operating manual
53
010-700_01
5. Initial operation, initialisation
Establishing mains voltage (400V control units)
▶ Connect the mains cable to the mains power supply.
▶ Move the main switch
(1)
to the ON position
✓
Initialisation begins automatically
• The device checks the electrical components,
• Voltage test of the standby batteries.
• Menu item |
3.10. Language|
appears.
Establishing mains voltage (230V control units)
▶ Insert the safety plug into the designated socket.
▶ Move the main switch
(1)
to the ON position
✓
Initialisation begins automatically
• The device checks the electrical components,
• Voltage test of the standby batteries.
• Menu item
|3.10. Language|
appears.
Switching on/off
Proceed as described for initial operation. Turn the main switch (1) to position
I (ON/OFF). Following a successful system test, |
0 System info|
appears
on the display and the green LED (3) indicates that the unit is ready for operation.
If the display does not show initialisation ( |
3.10. Language|
) the control
unit has already been initialised. In this case, the parameters set must be checked
or the unit must be reset to the factory setting (
|3.11 Reset|
). After the
factory settings have been reset, the control unit starts initialisation automatically.
Please note that the counter for the maintenance interval is not changed by a reset
to the factory settings.
1
2
3
4
5
Fig. [23]
Fault displays
Read off
message
If a state occurs which triggers a message (e.g. fault on a pump,
wastewater level has reached alarm level), the alarm LED (5) will
light up. A plain text fault message may be shown on the display.
Switch off
the acoustic
alarm
Press the alarm key (4) briefly.
Acknowledge
the alarm
Pressing the alarm (4) for 5 s acknowledges the alarm. The
message disappears, the acknowledgement is noted in the log
book.