background image

 

 

1.0  IMPORTANT SAFETY ADVICE 

 
 

Please  read  and  understand  this  manual  before  installing,  operating  or  servicing  the 
furnace.
    To  ensure  you  have  a  clear  understanding  of  the  operating  procedures  of  the  unit 
please take the time to read the IMPORTANT SAFETY ADVICE section of this manual. 

 

  Use only with Natural gas or Propane gas. Refer to the furnace rating plate. 

  Install  this  furnace  only  in  a  location  and  position  as  specified  in  Section  3  of 

these instructions. 

  Provide  adequate  combustion  and  ventilation  air  to  the  furnace  space  as 

specified in Section 3 of these instructions. 
 
WARNING 
FIRE OR EXPLOSION HAZARD 
Never  test  for  gas  leaks  with  an  open  flame.  Use  a  commercially  available  soap 
solution made specifically for the detection of leaks to check all connections, as 
specified in Section 5 of these instructions. 

 

  Always  install  furnace  to  operate  within  the  furnace’s  intended  temperature-rise 

range with a duct system that has an external static pressure within the allowable 
range, as specified in Section 5 of these instructions. See furnace rating plate. 

  When  a  furnace  is  installed  so  that  supply  ducts  carry  air  circulated  by  the 

furnace to areas outside the space containing the furnace, the return air shall also 
be  handled  by  duct(s)  sealed  to  the  furnace  casing  and  terminating  outside  the 
space containing the furnace. 

  This gas-fired furnace is not intended for installation in a residential garage. 

  This  furnace  is  not  factory  approved  for  installation  at  altitude  higher  than  2000 

feet. 

  Excessive  exposure  to  contaminated  combustion  air  will  result  in  safety  and 

performance related problems.  
 

o

  Sample List of Contaminants to be Avoided 

  The recommended source of combustion air is to use the outdoor air 

supply.  However,  the  use  of  indoor  air  in  most  applications  is 
acceptable except as follows: 

  1.  If  the  furnace  is  installed  in  a  confined  space  it  is 

recommended  that  the  necessary  combustion  air  come  from 
the  outdoors  by  way  of  attic,  crawl  space,  air  duct,  or  direct 
opening. 

  2.  If  outdoor  combustion  air  is  used,  there  must  be  no 

exposure to the installations or substances listed in “3” below. 

  3.  The  following  types  of  installation  may  require  OUTDOOR 

AIR for combustion, due to chemical exposures: 

o

  - Commercial buildings 

o

  - Buildings with indoor pools 

o

  - Furnaces installed in laundry rooms 

Summary of Contents for ECLIPSE 3T

Page 1: ...T INSTALLATIONS MUST MEET ALL LOCAL AND FEDERAL CODES THAT MAY DIFFER FROM THIS MANUAL Please read the manual in its entirety before beginning installation This manual must be kept with the furnace fo...

Page 2: ...2 GAS FIRED FURNACE LIGHTING INSTRUCTIONS 18 5 3 TECHNICAL INFORMATION SET UP 19 6 0 FURNACE OPERATION AND SETTINGS 21 6 1 BLOWER SETTING 21 6 2 FAN TIMER CONTROL BOARD ST9103 A 1028 22 6 3 ST9103 A...

Page 3: ...injury or death Do not store or use gasoline or other flammable vapors or liquid in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS o Do not try to light the appliance o Do no...

Page 4: ...rating plate When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s seale...

Page 5: ...MABLE VAPOURS AND LIQUIDS IN THE VICINITY OF THIS UNIT OR ANY OTHER APPLIANCE DANGER Do not use this furnace as a construction heater Use of this furnace as a construction heater exposes it to abnorma...

Page 6: ...re 0 5 wc Maximum cooling unit capacity 3 0 tons 5 0 Tons Maximum air temperature rise See pages 19 20 and 33 High Limit temperature 185 F Thermostat anticipator See thermostat instructions MOTOR BLOW...

Page 7: ...6 PLENUM GEMINI 3T 5T REAR FRONT Cold air return 19 x 20 483 x 508 mm Hot air supply 23 7 8 x 20 606 x 508 mm Plenum spacing 3T 1 3 4 45mm 5T 2 3 4 70mm GEMINI 3T 5T FRONT KLF GEMINI 3T 5T REAR KLR...

Page 8: ...7 PLENUM ECLIPSE 3T REAR FRONT Cold air return 18 x 20 3 4 457 x 527 mm Hot air supply 18 x 21 3 4 457 x 552 mm Plenum spacing 2 50mm ECLIPSE 3T FRONT KLF ECLIPSE 3T REAR KLR...

Page 9: ...combination gas valve inlet using new clean black iron pipe and malleable iron fittings only Do not use copper brass cast iron or galvanized pipe or fittings Provide support for gas piping Do not rest...

Page 10: ...mbination gas valve to gas pressures in excess of 14 W C The valve has a safety mechanism that interrupt the flow of gas over 14 W C In any event higher pressure could damage the valve seat resulting...

Page 11: ...ion Enough combustion air should be provided to the gas fired furnace in accordance with the section Air for combustion and ventilation of the National Fuel Gas Code ANSI Z223 1 NFPA 54 or clause 8 2...

Page 12: ...ace is removed from a common venting system the common venting system is likely to be too large for proper venting of the appliances connected to it At the time of removal of the existing furnace the...

Page 13: ...nd Air Supply for Appliances and Appendix C Vent Sizing Tables for Category I Natural Gas and Propane Appliances of the Natural Gas and Propane Installation Code CSA B149 1 the local building codes fu...

Page 14: ...FUEL GAS CODE ANDSI Z223 1 NFPA 54 AND OR NATIONAL GAS AND PROPANE INSTALLATION CODE CAN CSA B149 1 The temperature at the entrance of the chimney can be increased by insulating the flue pipe between...

Page 15: ...tion box Install a manual shut off switch at the door or stairway to furnace room so furnace can be shut off remotely The furnace must be electrically grounded in accordance with local codes or in the...

Page 16: ...the blockage has been corrected Installation 1 Drill a 5 8 hole in to the flue vent pipe near the appliance breech connection 2 This hole must be before the draft regulator vertically or horizontally...

Page 17: ...o ensure there is enough draft in the chimney and venting pipes AIR CONDITIONING An air conditioning coil may be installed on the supply side only Coils installed on the return side will cause condens...

Page 18: ...ion in section 5 2 below o In the section Combustion head settings disregard the table and use the information in section 5 2 below o In the section Manifold pressures disregard the table and use the...

Page 19: ...t off valve that you closed a few steps back Press the red button on the ignition control The burner should then retry its ignition and light the burner If this sequence is not respected consult the b...

Page 20: ...M HIGH M HIGH HIGH M HIGH HIGH HIGH Energy Star ECM motor 0 2 wc to 0 5 wc static pressure Temperature Rise F 40 70 45 75 55 85 55 85 55 85 60 85 Blower Speed M LOW M LOW M LOW M LOW M LOW M LOW Stati...

Page 21: ...on PSC motor info Temperature Rise F 55 85 55 85 55 85 55 85 55 85 55 85 Blower Speed 0 2 wc M LOW M HIGH M HIGH M LOW M HIGH M HIGH Blower Speed 0 5 wc M HIGH HIGH HIGH M HIGH HIGH HIGH Energy Star E...

Page 22: ...heck that the furnace starts and operates as usual OPERATION If the furnace system fails to operate or operates in an unusual manner call your service technician If the burner fails to operate at any...

Page 23: ...cold or too warm at the end of the heating cycle after the burner has turned off adjust the FAN OFF dip switch on fan timer control board Refer to the next figure FAN OFF Dip Switch OFF CYCLE AIR CIRC...

Page 24: ...s according to adjusted FAN OFF Dip switch selection ST9103 Cooling Sequence 1 Thermostat calls for cooling 2 Blower starts immediately 3 Cooling unit starts 4 Blower stops immediately after cooling d...

Page 25: ...l Yes Move to next step No Check for bad connection Yes Move to next step No Change Transformer 3 Electronic Fan control Check for 24 Volts between R and C Yes Move to next step No Change the electron...

Page 26: ...r No Change the electronic fan control 6 Blower Low speed Check if the constant low speed switch is ON Check for 120 Volts at the CONT terminal on the electronic fan control Yes Move to next step No C...

Page 27: ...the electronic fan control 7 0 SERVICE WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous operation serious injury death or property...

Page 28: ...base panel bracket 6 Slide the blower toward you and then lift the blower straight up Shift the blower out of the furnace Put back the blower assembly using the reverse procedure Ensure wiring and gro...

Page 29: ...R ECLIPSE 3T FRONT ILLUSTRATION SAME STEPS for the GEMINI Step 1 Remove breech plate Step 2 Remove baffles Step 3 Clean the round tubes if needed use a 2 diameter brush Step 4 Remove burner Step 5 Cle...

Page 30: ...as supplied instructions for servicing and maintenance should be performed as instructed Riello 40 G120 Gas Burner Carlin EZGas PRO Burner Burner PERFORM COMBUSTION TEST Perform an annual combustion c...

Page 31: ...30 8 0 ELECTRICAL WIRING DIAGRAMS HEATING COOLING Connection for Carlin Burner check the Carlin burner instruction manual...

Page 32: ...31 HEATING ONLY 2 WIRES THERMOSTAT Connection for Carlin Burner check the Carlin burner instruction manual Riello burner electrical connection see page 30...

Page 33: ...e address START UP TEST RESULTS Size of unit Btu h Input Manifold Pressure Chimney__________ DVSystem__________ Combustion Results CO2 Chimney draft W C Ambient temperature F Gross flue temperature F...

Page 34: ...Supply Pressure Ps Return Pressure Pr A C Coil Total Resistance Reading A C coil total resistance Coil Pressure Pc Supply Pressure Ps Temperature Rise Reading Temperature rise Supply Temp Ts Return T...

Page 35: ...feet facility Kerr products are sold across Canada through a wide distribution network Our team of engineers designers and technicians continually research and develop products to go beyond the demand...

Reviews: