background image

11 

 

PLACEMENT & VENTING

 

 

THE INSTALLATION OF YOUR GAS-FIRED FURNACE MUST CONFORM TO 
THE  REQUIREMENT  OF  THE  AUTHORITY  HAVING  JURISDICTION  OR  IN 
THE  ABSENCE OF SUCH REQUIREMENTS, TO THE NATIONAL FUEL GAS 
CODE  ANDSI  Z223.1/NFPA  54  AND/OR  NATIONAL  GAS  AND  PROPANE 
INSTALLATION CODE CAN/CSA B149.1. 

 

 

FLOOR SUPPORT  COMBUSTIBLE  –  If  required,  support  furnace  on  five  (5)  concrete 

blocks.    Make  sure  the  center  of  the  furnace  base  is  supported.    For  a 
furnace installed on a combustible floor, consult the applicable code and 
authorities having jurisdiction on this application.  The floor must support 
the weight. 

 

CHIMNEY/VENT 

Breech  is  certified  for  5”  vent  pipe.    Keep  vent/flue  pipe  as  short  as 
possible  with  min.  1/4”  per  foot  upward  slope.    Vent/flue  pipes  MUST 
NOT pass through a ceiling.  Maximum flue gas temperature is 480°F. 

 
ADDITIONAL CHIMNEY INFORMATIONS 
 
WARNING 

CARBON MONOXIDE POISONING HAZARD 

Failure  to follow the  steps outlined below for  each  appliance  connected  to  the  venting 
system  being  placed  into  operation  could  result  in  carbon  monoxide  poisoning  or 
death. 

When  an  existing  furnace  is  removed  from  a  common  venting  system,  the  common  venting 
system is likely to be too large for proper venting of the appliances connected to it. At the time 
of removal of the existing furnace, the following steps shall be followed  with EACH appliance 
remaining  connected  to  the  common  venting  system,  while  the  other  appliances  remaining 
connected to the common venting system are not in operation: 

1.  Seal any unused openings in the venting system. 
2.  Visually  inspect  the  venting  system  for  proper  size  and  horizontal  pitch  and  determine 

there is no blockage or restriction, leakage, corrosion and other deficiencies which could 
cause an unsafe operation. 

3.  Insofar as is practical, close all building doors and windows and all doors between the 

space in which the appliances remaining connected to the common venting system are 
located  and  other spaces of the building. Turn on clothes dryer and any appliance not 
connected  to  the  common  venting  system.  Turn  on  any  exhaust  fans,  such  as  range 
hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate 
a summer exhaust fan. Close fireplace dampers. 

4.  Place in operation the appliance being inspected. Follow the lighting instructions. Adjust 

thermostat operation so appliance will operate continuously. 

Summary of Contents for ECLIPSE 3T

Page 1: ...T INSTALLATIONS MUST MEET ALL LOCAL AND FEDERAL CODES THAT MAY DIFFER FROM THIS MANUAL Please read the manual in its entirety before beginning installation This manual must be kept with the furnace fo...

Page 2: ...2 GAS FIRED FURNACE LIGHTING INSTRUCTIONS 18 5 3 TECHNICAL INFORMATION SET UP 19 6 0 FURNACE OPERATION AND SETTINGS 21 6 1 BLOWER SETTING 21 6 2 FAN TIMER CONTROL BOARD ST9103 A 1028 22 6 3 ST9103 A...

Page 3: ...injury or death Do not store or use gasoline or other flammable vapors or liquid in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS o Do not try to light the appliance o Do no...

Page 4: ...rating plate When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s seale...

Page 5: ...MABLE VAPOURS AND LIQUIDS IN THE VICINITY OF THIS UNIT OR ANY OTHER APPLIANCE DANGER Do not use this furnace as a construction heater Use of this furnace as a construction heater exposes it to abnorma...

Page 6: ...re 0 5 wc Maximum cooling unit capacity 3 0 tons 5 0 Tons Maximum air temperature rise See pages 19 20 and 33 High Limit temperature 185 F Thermostat anticipator See thermostat instructions MOTOR BLOW...

Page 7: ...6 PLENUM GEMINI 3T 5T REAR FRONT Cold air return 19 x 20 483 x 508 mm Hot air supply 23 7 8 x 20 606 x 508 mm Plenum spacing 3T 1 3 4 45mm 5T 2 3 4 70mm GEMINI 3T 5T FRONT KLF GEMINI 3T 5T REAR KLR...

Page 8: ...7 PLENUM ECLIPSE 3T REAR FRONT Cold air return 18 x 20 3 4 457 x 527 mm Hot air supply 18 x 21 3 4 457 x 552 mm Plenum spacing 2 50mm ECLIPSE 3T FRONT KLF ECLIPSE 3T REAR KLR...

Page 9: ...combination gas valve inlet using new clean black iron pipe and malleable iron fittings only Do not use copper brass cast iron or galvanized pipe or fittings Provide support for gas piping Do not rest...

Page 10: ...mbination gas valve to gas pressures in excess of 14 W C The valve has a safety mechanism that interrupt the flow of gas over 14 W C In any event higher pressure could damage the valve seat resulting...

Page 11: ...ion Enough combustion air should be provided to the gas fired furnace in accordance with the section Air for combustion and ventilation of the National Fuel Gas Code ANSI Z223 1 NFPA 54 or clause 8 2...

Page 12: ...ace is removed from a common venting system the common venting system is likely to be too large for proper venting of the appliances connected to it At the time of removal of the existing furnace the...

Page 13: ...nd Air Supply for Appliances and Appendix C Vent Sizing Tables for Category I Natural Gas and Propane Appliances of the Natural Gas and Propane Installation Code CSA B149 1 the local building codes fu...

Page 14: ...FUEL GAS CODE ANDSI Z223 1 NFPA 54 AND OR NATIONAL GAS AND PROPANE INSTALLATION CODE CAN CSA B149 1 The temperature at the entrance of the chimney can be increased by insulating the flue pipe between...

Page 15: ...tion box Install a manual shut off switch at the door or stairway to furnace room so furnace can be shut off remotely The furnace must be electrically grounded in accordance with local codes or in the...

Page 16: ...the blockage has been corrected Installation 1 Drill a 5 8 hole in to the flue vent pipe near the appliance breech connection 2 This hole must be before the draft regulator vertically or horizontally...

Page 17: ...o ensure there is enough draft in the chimney and venting pipes AIR CONDITIONING An air conditioning coil may be installed on the supply side only Coils installed on the return side will cause condens...

Page 18: ...ion in section 5 2 below o In the section Combustion head settings disregard the table and use the information in section 5 2 below o In the section Manifold pressures disregard the table and use the...

Page 19: ...t off valve that you closed a few steps back Press the red button on the ignition control The burner should then retry its ignition and light the burner If this sequence is not respected consult the b...

Page 20: ...M HIGH M HIGH HIGH M HIGH HIGH HIGH Energy Star ECM motor 0 2 wc to 0 5 wc static pressure Temperature Rise F 40 70 45 75 55 85 55 85 55 85 60 85 Blower Speed M LOW M LOW M LOW M LOW M LOW M LOW Stati...

Page 21: ...on PSC motor info Temperature Rise F 55 85 55 85 55 85 55 85 55 85 55 85 Blower Speed 0 2 wc M LOW M HIGH M HIGH M LOW M HIGH M HIGH Blower Speed 0 5 wc M HIGH HIGH HIGH M HIGH HIGH HIGH Energy Star E...

Page 22: ...heck that the furnace starts and operates as usual OPERATION If the furnace system fails to operate or operates in an unusual manner call your service technician If the burner fails to operate at any...

Page 23: ...cold or too warm at the end of the heating cycle after the burner has turned off adjust the FAN OFF dip switch on fan timer control board Refer to the next figure FAN OFF Dip Switch OFF CYCLE AIR CIRC...

Page 24: ...s according to adjusted FAN OFF Dip switch selection ST9103 Cooling Sequence 1 Thermostat calls for cooling 2 Blower starts immediately 3 Cooling unit starts 4 Blower stops immediately after cooling d...

Page 25: ...l Yes Move to next step No Check for bad connection Yes Move to next step No Change Transformer 3 Electronic Fan control Check for 24 Volts between R and C Yes Move to next step No Change the electron...

Page 26: ...r No Change the electronic fan control 6 Blower Low speed Check if the constant low speed switch is ON Check for 120 Volts at the CONT terminal on the electronic fan control Yes Move to next step No C...

Page 27: ...the electronic fan control 7 0 SERVICE WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous operation serious injury death or property...

Page 28: ...base panel bracket 6 Slide the blower toward you and then lift the blower straight up Shift the blower out of the furnace Put back the blower assembly using the reverse procedure Ensure wiring and gro...

Page 29: ...R ECLIPSE 3T FRONT ILLUSTRATION SAME STEPS for the GEMINI Step 1 Remove breech plate Step 2 Remove baffles Step 3 Clean the round tubes if needed use a 2 diameter brush Step 4 Remove burner Step 5 Cle...

Page 30: ...as supplied instructions for servicing and maintenance should be performed as instructed Riello 40 G120 Gas Burner Carlin EZGas PRO Burner Burner PERFORM COMBUSTION TEST Perform an annual combustion c...

Page 31: ...30 8 0 ELECTRICAL WIRING DIAGRAMS HEATING COOLING Connection for Carlin Burner check the Carlin burner instruction manual...

Page 32: ...31 HEATING ONLY 2 WIRES THERMOSTAT Connection for Carlin Burner check the Carlin burner instruction manual Riello burner electrical connection see page 30...

Page 33: ...e address START UP TEST RESULTS Size of unit Btu h Input Manifold Pressure Chimney__________ DVSystem__________ Combustion Results CO2 Chimney draft W C Ambient temperature F Gross flue temperature F...

Page 34: ...Supply Pressure Ps Return Pressure Pr A C Coil Total Resistance Reading A C coil total resistance Coil Pressure Pc Supply Pressure Ps Temperature Rise Reading Temperature rise Supply Temp Ts Return T...

Page 35: ...feet facility Kerr products are sold across Canada through a wide distribution network Our team of engineers designers and technicians continually research and develop products to go beyond the demand...

Reviews: