11
PLACEMENT & VENTING
THE INSTALLATION OF YOUR GAS-FIRED FURNACE MUST CONFORM TO
THE REQUIREMENT OF THE AUTHORITY HAVING JURISDICTION OR IN
THE ABSENCE OF SUCH REQUIREMENTS, TO THE NATIONAL FUEL GAS
CODE ANDSI Z223.1/NFPA 54 AND/OR NATIONAL GAS AND PROPANE
INSTALLATION CODE CAN/CSA B149.1.
FLOOR SUPPORT COMBUSTIBLE – If required, support furnace on five (5) concrete
blocks. Make sure the center of the furnace base is supported. For a
furnace installed on a combustible floor, consult the applicable code and
authorities having jurisdiction on this application. The floor must support
the weight.
CHIMNEY/VENT
Breech is certified for 5” vent pipe. Keep vent/flue pipe as short as
possible with min. 1/4” per foot upward slope. Vent/flue pipes MUST
NOT pass through a ceiling. Maximum flue gas temperature is 480°F.
ADDITIONAL CHIMNEY INFORMATIONS
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting
system being placed into operation could result in carbon monoxide poisoning or
death.
When an existing furnace is removed from a common venting system, the common venting
system is likely to be too large for proper venting of the appliances connected to it. At the time
of removal of the existing furnace, the following steps shall be followed with EACH appliance
remaining connected to the common venting system, while the other appliances remaining
connected to the common venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine
there is no blockage or restriction, leakage, corrosion and other deficiencies which could
cause an unsafe operation.
3. Insofar as is practical, close all building doors and windows and all doors between the
space in which the appliances remaining connected to the common venting system are
located and other spaces of the building. Turn on clothes dryer and any appliance not
connected to the common venting system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate
a summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust
thermostat operation so appliance will operate continuously.