The d-c output connectors of the MST power supplies installed in the rack adapter are accessed
via connector extenders (J1 - J9) mounted on the backplate assembly.

FIGURE 2.    RA 55 BACKPLATE ASSEMBLY

1.3

MECHANICAL

The rack adapter is pre-drilled to accept chassis slides. It is equipped with four metal foot
attachments, rack adapter handles, and mounting ears. The rack adapter can use 18-inch
(457.2 mm) Jonathan Model 110-QD-18-2 chassis slides. The rack adapter can be equipped
with optional 1/9 rack blank filler panels (Kepco Model RFP 55-1) if the full complement of nine
power supplies is not utilized.

Mechanical dimensions, material, and finish of the Kepco Model RA 55 Rack Adapter are pro-
vided in Figure 5.

1.4

COOLING

The MST power supplies mounted within the rack adapter are maintained within their operating
temperature range by means of internal cooling fans. ALL INLET AND EXHAUST OPENINGS
AT THE TOP, BOTTOM AND REAR OF THE RACK ADAPTER CASE MUST BE KEPT CLEAR
OF OBSTRUCTION TO ENSURE PROPER AIR ENTRY AND EXHAUST. Care must be taken
that the ambient temperature, which is the temperature of the air immediately surrounding the
rack adapter, does not rise above the specified limits for the operating load conditions of the
installed MST power supplies. Kepco recommends providing a 1U (1.75 in.) space above and
below the rack adapter.

1.5

ACCESSORIES

Table 1 lists the accessories provided with the RA 55 Rack Adapter. A controller and up to 27
MST, MAT or MBT Power Modules can be connected in a daisy chain configuration as shown in
Figure 3. The last (unused) power module control bus outlet (in the daisy chain) must be termi-
nated with an IEEE1118 Control Bus Terminator (not supplied, see Table 1); if only one Rack
Adapter is used, connect the terminator to either connector J12 or J13. Note that IEEE 1118

Summary of Contents for RA55

Page 1: ...ion Office in New York 718 461 7000 requesting the correct revision for your par ticular model and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can b...

Page 2: ...355 USA Importer s Name and Address Type of Equipment Rack Adapter Model No PRODUCT MODEL NUMBER Year of Manufacture I the undersigned declare that the product specified above when used in conjunction...

Page 3: ...wire power systems This equipment must be installed within a suitably wired equipment rack utilizing a three wire grounded mains connection See wiring section of this manual for complete electrical w...

Page 4: ...product s rear panel To reconfigure the product input for other nominal mains voltages as listed herein the product must be modified by a trained service technician The PROTECTIVE EARTHING CONDUCTOR T...

Page 5: ...ADAPTER 2 1 Input Power 6 2 1 1 General 6 2 1 2 Safety Grounding 6 2 1 3 Source Power Connections 6 2 2 Load Connections 7 2 3 Control Signal Connections 7 2 4 Slot 9 Configuration 7 1 Kepco Model RA...

Page 6: ......

Page 7: ...lity Dual a c input terminal blocks J10 and J11 on the backplate assembly Figure 2 distribute input power to nine PCB mounted a c input control bus power connectors P1 P9 as shown in Figure 4 Terminal...

Page 8: ...their operating temperature range by means of internal cooling fans ALL INLET AND EXHAUST OPENINGS AT THE TOP BOTTOM AND REAR OF THE RACK ADAPTER CASE MUST BE KEPT CLEAR OF OBSTRUCTION TO ENSURE PROPE...

Page 9: ...B connector Kepco P N 142 0225 one 5 pin DIN connector Kepco P N 142 0308 Kepco 118 0749 Not supplied Cable BIT bus 2m long two 5 pin DIN connectors Kepco P N 142 0308 Kepco 118 0699 Not supplied Term...

Page 10: ...4 RA55 032615 FIGURE 4 RA 55 INTERCONNECTIONS AND INPUT OUTPUT PIN CONNECTIONS...

Page 11: ...RA55 032615 5 FIGURE 5 MECHANICAL OUTLINE DRAWING OF THE RA 55 RACK ADAPTER...

Page 12: ...rules are described in detail in the following paragraphs All interconnections are accomplished at the backplate assembly Figure 2 Refer to Figure 3 for RA 55 interconnections and input output connec...

Page 13: ...00V rms can result in source current in excess of 15A at terminal block J10 or J11 For this reason Kepco rec ommends use of 14 AWG wire minimum in fully populated systems For lower system power config...

Page 14: ...efore installing MST Power Module in RA 55 Rack Adapter pull out the two captive thumb screws at the front of the Power Module and turn counterclockwise until the threads engage FIGURE 6 LOAD CONNECTO...

Reviews: