background image

2

228-1533 REV 15

 083013

KEPCO, INC. 

   

 131-38 SANFORD AVENUE 

 

  FLUSHING, NY. 11355 U.S.A.

 

  TEL (718) 461-7000

   

 FAX (718) 767-1102

  

http://www.kepcopower.com   

 

 email: [email protected]

FIGURE 1.  24V MODEL PEAK CURRENT REQUIREMENTS (

REMOTE ON-OFF.  

Remote on-off (X and Y models

only) is via ±RC assigned to pins of the RA 19-(X)B I/O
connector: off = no voltage, short circuit, or 0 to 0.8V, on =
4.5 to 12.5V (or 12.5 to 24.5V via 1.5K Ohms). To reverse
on-off polarity contact Kepco. There is no isolation
between ±RC, d-c output and alarm circuit. Refer to the
applicable RA 19-(X)B Manual for details.

CURRENT MONITOR. 

Current monitor (C and Y

models only) is via ±IMON assigned to pins of the RA 19-
(X)B I/O connector. Monitored Output Current (Amps) =
Voltage drop across R

EQ

 (mVolts) / R

EQ

 (mOhms) where

R

EQ

 is the sum of R

S

 (see Table 2) + trace resistance to

point where current monitor is connected, approximately
4mOhms. The voltage drop across R

EQ

 is measured

across ± IMON pins (requires millivoltmeter, range 0 to
250mV). Accuracy is ±10%; contact Kepco if greater
accuracy is required. There is no isolation between
±IMON, alarm circuit and d-c output. Refer to the applica-
ble RA 19-(X)B Manual for details.

ALARM CIRCUIT.  

Any condition which causes the

unit to be out of specified voltage/current ranges (includ-
ing overvoltage, overcurrent, overtemperature, open
sense line, ac input line failure, etc.) results in an alarm.
All models include an isolated internal relay offering nor-
mally closed and normally open contacts referenced to an
isolated common. These contacts are rated for 1A at 30V
d-c and 0.5A at 125V a-c. These contacts may be used to
configure “close on failure” or “open on failure” alarm cir-
cuits (see Figure 3 for typical alarm circuits). Refer to the
applicable RA 19-(X)B Manual for details about the follow-
ing: 1) normally open (close on failure) contacts are not
available if ±RC is used on X and Y suffix models, 2)
alarm signals are not isolated on C, X and Y models and
3) alarm configurations for multiple power supplies. 

KEYING. 

Keying of the power supply is established at

the factory. The output voltage determines which keyway
is open. When the corresponding rack adapter key (pin) is
installed by the user, only a power supply of the correct
voltage can be inserted in the rack adapter slot.

FIGURE 2.  HSF-PFC 100 WATT POWER SUPPLIES (8) INSTALLED IN RA 19-8B RACK ADAPTER

3043527

I

1

I

2

T

t

D=(t/T)

The standard 24V Model (no options) can supply Peak
current listed in Table 1 if the four conditions listed below
are met. These models include thermal protection, volt-
age shutdown type. Restart by removing a-c input; after
sufficient cooling, reapply a-c input (wait at least 30 sec-
onds).

1. Time: t 

≤ 

10 Seconds

2. 

I

1

 

≤ 

Peak Current (Amperes)

3. Effective Current:

 

 

 Rated current (Amperes)

4. Effective Power P 

 Maximum Power (Watts)

    (output RMS current x output voltage)

DI1

2

I D

(

)

I2

2

×

+

Summary of Contents for HSF 3.3-20PFC

Page 1: ...ard models and Section IV on page 6 suffix C T X and Y OPTIONS Options are identified by suffix T PFCT offers improved efficiency and less weight C PFCC offers current monitoring via an integral curre...

Page 2: ...se line ac input line failure etc results in an alarm All models include an isolated internal relay offering nor mally closed and normally open contacts referenced to an isolated common These contacts...

Page 3: ...e operating at between 10 to 100 of rated output current If current to the load goes below 10 for each unit in cur rent share mode all MASTER ON lights may go on see load effect specifications this in...

Page 4: ...emperature effects 0 9 typ 1 8 max Time Effect 1 2 hr 8 hr at 25o C 0 2 typ 0 5 max RECOVERY CHARACTERISTICS A step load change from 50 to 100 produces less than 4 output excursion Recovery occurs to...

Page 5: ...c SAFETY Units are designed to meet UL60950 3rd Edi tion CSA 22 2 No 60950 60950 1 and EN60950 and are CE marked per the Low Voltage Directive LVD 73 23 EEC and 93 68 EEC The standards do not apply wi...

Page 6: ...rature effects 0 9 typ 1 8 max Time Effect 1 2 hr 8 hr at 25o C 0 2 typ 0 5 max TABLE 2 OUTPUT RATINGS AND SPECIFICATIONS HSF PFC 100W SERIES SUFFIX C T X Y ONLY MODEL HSF 3 3 25 1 2 7 PFCC PFCT PFCX...

Page 7: ...TION RESISTANCE Between input and ground output and ground input and output 100 Megohms min 500V d c LEAKAGE CURRENT per IEC 950 and UL 1950 0 13mA typ 0 19 mA maximum 120V a c 0 45 mA maximum 240V a...

Page 8: ...TION DO NOT repeatedly toggle the POWER on off switch as this may cause unit to fault When output voltage is available the green VDC ON LED is on While monitoring output voltage at the front panel tes...

Page 9: ...ORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com 083013 228 1533 REV 15 9 FIGURE 6 HSF PFC 100W INCLUDING SUFFIX C T X AND Y POWER S...

Reviews: