background image

10

HSF(A) 600W 040215

3.4.2 REMOTE VOLTAGE CONTROL 

Output voltage can be controlled remotely by means of an external voltage or resistance instead
of by Vadj. Configure the DIP switches as follows:

SW1: pos1 to ON, pos2 to ON; SW2: pos 1 to OFF, Pos2 to OFF

NOTE: Configuring the unit for remote output voltage control disables the front panel Vadj con-

trol. To restore Vadj control, configure the DIP switches per PAR. 3.4.1.

When DIP switch positions 1 and 2 are configured as noted above, output voltage can be adjusted
by either an external trimmer pot (resistance) or by an external variable voltage source as shown
in Figure 7. At the rack adapter I/O connector use a shielded wire 6.6 feet (2M) maximum in
length, for connection of pin 2 (REF, Reference), pin 12 (RV, Remote Voltage), and pin 10 (–COM,
Common) of the rack adapter I/O connector to the trimmer control or external voltage source.

Using External Voltage to Control the Output.

 Connect the external voltage source across the

RV and –COM pins as shown in Figure 7B. By adjusting an external 0 to 6V voltage source (0 to
5.5V for the 48V model), the HSF (A, AM) output voltage can be adjusted within the range specified
in Table 2. To ensure proper operation of the alarm relay, meter (AM Models only) and VDC ON/
ALARM indicator, do not adjust the external voltage below minimum listed in Table 5. 

Using External Resistance to Control the Output.

 Connect the unit to the RV, –COM and REF

pins as shown in Figure 7A. Suggested value for the trimmer control is 20K ohms. Referring to
Figure 7A, Resistor R is used to obtain minimum output voltage required to ensure proper opera-
tion of the alarm relay, meter (AM Models only) and VDC ON/ALARM indicator; see Table 5 for
values. 

NOTES: 1.

Output voltage may not adjust to 0V due to residual trimmer resistance.

2.  If remote output control is not implemented, the factory default for positions 1, 2

and 7 of DIP switches SW1 and SW2 must be restored (Figure 6A).

3.

It is possible that overvoltage protection may be triggered if the output voltage is
decreased to a low level very quickly when the power supply is at a low load 
condition.

FIGURE 6.  DIP SWITCH SETTINGS FOR CONTROL OF OUTPUT VOLTAGE

OFF

SW1

3043769

REF  1

RV  2

SW2

1

ON

2

1

2

OFF

1  REF

2  RV

ON

SW1

SW2

1

2

OFF

ON

1
2

OFF

ON

USING Vadj CONTROL

FRONT PANEL VOLTAGE CONTROL

A

B

(FACTORY DEFAULT)

REMOTE VOLTAGE CONTROL

OR VOLTAGE SOURCE

USING EXTERNAL TRIMPOT

REF  1

RV  2

2  RV

1  REF

TAB

7

7 VADJ

TO ZERO

NOTE: SWITCH POSITIONS NOT SHOWN HAVE NO EFFECT ON DESCRIBED FUNCTION.

Summary of Contents for HSF 12-53A

Page 1: ...el and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco Inc Data subject to change without...

Page 2: ...g Latches 15 4 Load Connection 16 5 Connecting Multiple Power Supplies 16 1 HSF A AM Rear Panel Connector and RA 19 4C Rack Adapter I O Connector 1 2 Power Rating Vs Temperature 3 3 Mechanical Outline...

Page 3: ...of 12V 15V 24V 28V or 48V They employ forward con version and power factor correction and are designed to operate in a fault tolerant power system Input voltage range is single phase 85 265V a c 47 63...

Page 4: ...see PAR 3 7 2 1 REF 15 Reference voltage When used with RV pin 18 allows all output voltages of paralleled slave supplies to be controlled by one voltage adjustment of a master power supply When REF...

Page 5: ...requires that DIP SW1 position 7 be set to ON Refer to Table 5 for mini mum conditions required to maintain proper operation of alarm relay meter AM Models only and VDC ON ALARM indicator 2 Using tri...

Page 6: ...0 2 Maximum 85 to 132V a c 170 to 265V a c Load Effect 0 6 Typical 1 Maximum default 0 6 Typical 1 Maximum see PAR 3 8 Individual Mode 0 100 load change Current Sharing 10 100 load change Temperature...

Page 7: ...a c 50 60Hz ambient temperature 40 C max RoHS Compliance RoHS versions available contact Kepco Sales for further information EMC Emission Conducted Designed to meet FCC Class B VCCI Class B EN55011 B...

Page 8: ...0 093 2 4 0 127 3 2 0 430 10 9 2 065 52 5 3 353 85 2 0 337 8 5 0 085 2 2 0 204 5 2 0 090 2 3 0 943 23 9 2 408 61 2 0 438 11 1 0 394 10 0 3 216 81 7 0 606 15 4 0 690 17 5 FRONT VIEW REAR VIEW SEE REAR...

Page 9: ...6 CSB 1 OFF Enables Current Share always off ON N A 6 CSB 1 OFF N A ON Enables Current Share always on 7 COM to S OFF Isolates COM from S ON Connects COM to S 7 VADJ to 0 OFF Vadj adjusts output per T...

Page 10: ...established at the factory The output voltage determines which key pins are installed see Figure 3 Detail A When the proper holes in the rack adapter are blocked by keying screws installed by the user...

Page 11: ...ore unit is removed from the rack adapter Retaining Latches 2 Prevents inadvertent removal of unit from rack adapter see PAR 3 9 AM Models only Voltage Current meter Monitors out put voltage or curren...

Page 12: ...pecified in Table 2 To ensure proper operation of the alarm relay meter AM Models only and VDC ON ALARM indicator do not adjust the external voltage below minimum listed in Table 5 Using External Resi...

Page 13: ...other unlike earlier non A HSF 600W models This return is connected to the power supply OUTPUT Please contact Kepco if appli cation requires remote control to be isolated from DC output or from PF si...

Page 14: ...wait until unit cools then set the POWER switch to ON The power supply cannot be reset using the remote ON OFF feature unless the power supply remains shut down for at least 40 seconds 3 6 2 OVERCURR...

Page 15: ...N ALARM indicator can be disabled by setting DIP switch 1 position 8 to OFF 3 7 2 ALARM SIGNALS Either of two options are available for signalling alarms isolated relay contacts factory default PAR 3...

Page 16: ...on the transistor cuts off and the collector emitter cir cuit is open Figure 12 is a timing diagram of the power fail signal The default state of the alarm is logic low The sink current for the optoco...

Page 17: ...in conjunction with the RA 19 4C rack adapters to prevent unauthorized or inadvertent module extraction from an operating power system The latch is engaged by loosening the cap head screw approximatel...

Page 18: ...e the difference between voltage settings of parallel con nected units should be less than 0 5 of the nominal voltage value of the units Output voltage adjustment should be done at same load for each...

Reviews: