background image

12

HSF 600W 042315

3.7.2 ALARM SIGNALS. 

Either of two options are available for signalling alarms: isolated relay contacts (factory default,
PAR. 3.7.2.1) or logic level alarm signals ±PF (PAR. 3.7.2.2). The ±PF logic level alarm option
must be used if the power supply is intended to operate below the minimum voltages listed in
Table 4.

3.7.2.1 INTERNAL ISOLATED RELAY ALARM

The first option, the factory default setting, uses an isolated internal relay offering normally closed
(NC) and normally open (NO) contacts referenced to an isolated common (AL COM). These con-
tacts may be used to configure “close on failure” or “open on failure” alarm circuits. (Refer to the
Series RA 19-4C Manual for alarm configurations for multiple HSF power supplies.) Setting posi-
tions 5 and 6 of the DIP switches as shown in Figure 9A selects this option. The NC (pin 6 of the
rack adapter I/O connector) and NO (pin 7) signals are referenced to Alarm common (pin 14).

3.7.2.2 OPTICALLY-COUPLED LOGICAL ALARM

The second option uses optically-coupled logic level alarm signals, +PF (pin 5 of the rack adapter
I/O connector) and -PF (pin 13), provided directly from the Kepco RKW power supply that is the
heart of the HSF. This option is selected by setting positions 5 and 6 of the DIP switches as shown
in Figure 9B. Use this option if the power supply will operate below the minimum voltages speci-
fied in Table 4.

FIGURE 9.  DIP SWITCH SETTINGS FOR OPTICALLY COUPLED LOGICAL ALARM

The logic alarm circuit is a diode transistor optical coupler (see Figure 10). The transistor is nor-
mally conducting. When the alarm is activated upon detection of power loss, overvoltage, fan
fault, overtemperature or overcurrent condition, the transistor cuts off and the collector emitter cir-
cuit is open. Figure 11 is a timing diagram of the power fail signal.

The default state of the alarm is logic low. The sink current for the optocoupler is 50mA maximum,
the maximum collector to emitter saturation voltage is 0.40 Volts, and the collector to emitter volt-
age is 40 volts maximum. The PF signals are isolated from the AC input and DC output.

3042878

5

5    +PF

+PF  5

5

SW1

-PF  6

6

SW2

6

6  -PF

OFF

ON

OFF

ON

USE N.O. AND N.C CONTACTS

(FACTORY DEFAULT)

OF INTERNAL RELAY

A

LOGICAL ALARM

USE OPTICALLY-COUPLED

B

(+PF AND -PF)

5

6

6

SW1

5

SW2

OFF

ON

ON

OFF

+PF  5

-PF  6

6  -PF

5  +PF

TAB

Summary of Contents for HSF 12-53

Page 1: ...rticular model and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco Inc Data subject to ch...

Page 2: ...ote Sensing 13 3 9 Retaining Latches 13 4 Load Connection 14 5 Connecting Multiple Power Supplies 14 5 1 Adjusting the Voltage 14 5 2 Parallel Connections Standard and C Models 14 1 HSF Rear Panel Con...

Page 3: ...pco s Series RA 19 4C rack adapters The RA 19 4C rack adapter accepts up to four 600W modules All input output connections are through a 24 pin connector that plugs in to the rack adapter All external...

Page 4: ...COM 14 Common contact of alarm relay see PAR 3 7 2 REF 15 Reference voltage When used with RV pin 18 allows all output voltages of paralleled slave supplies to be controlled by one voltage adjustment...

Page 5: ...Factor typ AC Input 100V 0 99 0 99 0 99 0 99 0 99 AC Input 200V 0 95 0 95 0 95 0 95 0 95 Ripple Noise 6 mV p p ripple 180 180 220 220 220 ripple noise 220 220 320 320 320 Sense Resistor IMON values Oh...

Page 6: ...1000 3 2 0 95 typical 200V a c max load nominal output per EN 61000 3 2 Transient Recovery excursion characteristic 4 maximum 50 to 100 load transient time 50 sec recovery time 1 ms maximum Stabilizat...

Page 7: ...2 No 60950 1 03 1st Edition 2006 07 EN 60950 RoHS Compliance Contact Kepco Sales for further information EMC Emission Conducted Designed to meet FCC Class B VCCI Class B EN55011 B EN55022 B EMC Emissi...

Page 8: ...e controlled either by the front panel Vadj control or by remote control using either an external trimpot or voltage source see PAR 3 4 4 288 108 9 5 218 132 5 1 500 38 1 0 093 2 4 14 667 372 5 5 040...

Page 9: ...eatedly toggle the power ON OFF switch as this may cause unit to fault NOTE The ON OFF switch must be set to OFF before removing unit from rack adapter If remote on off is not enabled see PAR 3 5 the...

Page 10: ...d in Table 2 see PAR 3 4 1 Not functional if remote voltage control is enabled see PAR 3 4 2 3 DC output test points Connect to voltmeter to monitor output voltage 4 OUTPUT RESET switch Used to recycl...

Page 11: ...shown in Figure 7A Suggested value for the trim mer control is 5K ohms Referring to Figure 7 A Resistor R is used to obtain minimum output voltage required to ensure proper operation of the alarm rel...

Page 12: ...DC output pins and a c input terminals FIGURE 8 DIP SWITCH SETTINGS FOR USING RESET BUTTON OR REMOTE ON OFF 3 6 PROTECTION CIRCUITS The following protection features are implemented in the HSF 600W Se...

Page 13: ...the OUTPUT RESET switch on the front panel or if the remote on off feature is in use see PAR 3 5 open the connection between the RC pins and then reconnect the pins The unit may also be restarted by t...

Page 14: ...he rack adapter I O connector and PF pin 13 provided directly from the Kepco RKW power supply that is the heart of the HSF This option is selected by setting positions 5 and 6 of the DIP switches as s...

Page 15: ...5 These latches work in conjunction with the RA 19 4C rack adapters to prevent unauthorized or inadvertent module extraction from an operating power system The latch is engaged by loosening the cap he...

Page 16: ...xcept one designated as the master and adjust to desired voltage using the front page trimmer and monitoring the front panel voltmeter Each slave must be adjusted to a slightly lower voltage than the...

Reviews: