background image

14

HSF 600W 042315

4

LOAD CONNECTION

Connect the load to (+) and (–) terminals at the rear panel of the Rack Adapter (see RA 19-4C
Instruction Manual for details).

5

CONNECTING MULTIPLE POWER SUPPLIES

All connections to multiple HSF power supplies must be made via the I/O mating connectors at
rear of the Rack Adapter or by the Rack Adapter DIP switches. These connections, including the
configuration of the two internal HSF DIP switches, are described in the Rack Adapter Instruction
manual, and include:

Using one power supply to control the output of multiple supplies.

Using parallel master/slave configurations (for increased current or redundancy) where
the user either predetermines the master or allows the load to determine which is the
master. These configurations also cover the use of the Current Balancing feature of the
HSF power supply. 

Using series configurations (for increased voltage).

Using open-on-fail or close-on-fail alarm schemes with multiple power supplies.

5.1

ADJUSTING THE VOLTAGE 

NOTE: Refer to the RA 19-4C Rack Adapter manual for alternatives to the standard master/

slave parallel configuration described below.

To adjust the paralleled units, turn off all the units except one (designated as the master) and
adjust to desired voltage using the front page trimmer and monitoring the front panel voltmeter. 

Each slave must be adjusted to a slightly lower voltage than the previous unit. The differ-
ence between the master and the lowest voltage slave must not exceed 2% of E

NOM

The voltage separation between master and subsequent slave(s) (V

SEP

) = 2% E

NOM

 / N

where N = number of units in parallel. 

Adjust the first slave V

SLAVE1

 to E

NOM

 - V

SEP

. Adjust the second slave V

SLAVE2

 to V

SLAVE1

 -   V

SEP

.

Adjust the third slave V

SLAVE3

 to V

SLAVE2

 - V

SEP

 and so on.

As an example, for three HSF 24-27 units in parallel, 2% of E

NOM

 is 0.48V and V

SEP

 is 0.48/3 =

0.16V. Turn off the master, then turn on another unit (slave 1) and adjust for 160mV less than the
master. Turn off slave 1 and turn on slave 2 and adjust for 160mV less than slave 1.

When all units are turned on, the unit adjusted to the highest voltage will be the master. If a unit
fails, the VDC ON indicator of that unit is either off or red.

5.2

PARALLEL CONNECTIONS, STANDARD AND C MODELS

When using parallel-connected standard (no suffix) and C Models, a minimum load is required to
avoid the slave becoming “idle.” When the slave is idle, the output is off, no lights are lit, and the
alarm is set. 

The minimum load (Amperes) = N x (I/10) 
   where N = the number of units in parallel, 
               I = Nominal current rating of individual power supply (Amperes). 

Summary of Contents for HSF 12-53

Page 1: ...rticular model and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco Inc Data subject to ch...

Page 2: ...ote Sensing 13 3 9 Retaining Latches 13 4 Load Connection 14 5 Connecting Multiple Power Supplies 14 5 1 Adjusting the Voltage 14 5 2 Parallel Connections Standard and C Models 14 1 HSF Rear Panel Con...

Page 3: ...pco s Series RA 19 4C rack adapters The RA 19 4C rack adapter accepts up to four 600W modules All input output connections are through a 24 pin connector that plugs in to the rack adapter All external...

Page 4: ...COM 14 Common contact of alarm relay see PAR 3 7 2 REF 15 Reference voltage When used with RV pin 18 allows all output voltages of paralleled slave supplies to be controlled by one voltage adjustment...

Page 5: ...Factor typ AC Input 100V 0 99 0 99 0 99 0 99 0 99 AC Input 200V 0 95 0 95 0 95 0 95 0 95 Ripple Noise 6 mV p p ripple 180 180 220 220 220 ripple noise 220 220 320 320 320 Sense Resistor IMON values Oh...

Page 6: ...1000 3 2 0 95 typical 200V a c max load nominal output per EN 61000 3 2 Transient Recovery excursion characteristic 4 maximum 50 to 100 load transient time 50 sec recovery time 1 ms maximum Stabilizat...

Page 7: ...2 No 60950 1 03 1st Edition 2006 07 EN 60950 RoHS Compliance Contact Kepco Sales for further information EMC Emission Conducted Designed to meet FCC Class B VCCI Class B EN55011 B EN55022 B EMC Emissi...

Page 8: ...e controlled either by the front panel Vadj control or by remote control using either an external trimpot or voltage source see PAR 3 4 4 288 108 9 5 218 132 5 1 500 38 1 0 093 2 4 14 667 372 5 5 040...

Page 9: ...eatedly toggle the power ON OFF switch as this may cause unit to fault NOTE The ON OFF switch must be set to OFF before removing unit from rack adapter If remote on off is not enabled see PAR 3 5 the...

Page 10: ...d in Table 2 see PAR 3 4 1 Not functional if remote voltage control is enabled see PAR 3 4 2 3 DC output test points Connect to voltmeter to monitor output voltage 4 OUTPUT RESET switch Used to recycl...

Page 11: ...shown in Figure 7A Suggested value for the trim mer control is 5K ohms Referring to Figure 7 A Resistor R is used to obtain minimum output voltage required to ensure proper operation of the alarm rel...

Page 12: ...DC output pins and a c input terminals FIGURE 8 DIP SWITCH SETTINGS FOR USING RESET BUTTON OR REMOTE ON OFF 3 6 PROTECTION CIRCUITS The following protection features are implemented in the HSF 600W Se...

Page 13: ...the OUTPUT RESET switch on the front panel or if the remote on off feature is in use see PAR 3 5 open the connection between the RC pins and then reconnect the pins The unit may also be restarted by t...

Page 14: ...he rack adapter I O connector and PF pin 13 provided directly from the Kepco RKW power supply that is the heart of the HSF This option is selected by setting positions 5 and 6 of the DIP switches as s...

Page 15: ...5 These latches work in conjunction with the RA 19 4C rack adapters to prevent unauthorized or inadvertent module extraction from an operating power system The latch is engaged by loosening the cap he...

Page 16: ...xcept one designated as the master and adjust to desired voltage using the front page trimmer and monitoring the front panel voltmeter Each slave must be adjusted to a slightly lower voltage than the...

Reviews: