background image

12

228-1915

 053119

KEPCO, INC. 



 131-38 SANFORD AVENUE 



  FLUSHING, NY. 11355 U.S.A.



  TEL (718) 461-7000



 FAX (718) 767-1102

http://www.kepcopower.com   



 email: [email protected]

DETERMINING HOW THE UNIT RESPONDS 

WHEN OUTPUT IS OFF (LOAD TYPE) 

 The

BOP supports three Load Type selections (see Table 4)
which determine how the power supply responds when
the output is off: ACTIVE, RESISTIVE and BATTERY.
The Load Type selection does not affect the settings of
the power supply for ON state; it only affects the main
internal reference level and the protection levels during
the OFF state. 

WARNING

For inductive loads, and especially
superconducting magnet type
loads, the inherent offset of the
BOP in the OFF state may generate
significant current in the circuit. A
properly rated switch in parallel
with a resistor must be connected
between the power supply and the

load. The switch must be open and
the BOP front panel LCD must read
0V, 0A before removing or installing
connections between BOP and
load. 

Active.

 Active mode (default setting) is necessary for

the power supply to function properly and safely with
inductive loads and constant-current-type active elec-
tronic loads. Active mode can also be used with resis-
tive loads. Table 4 indicates how the power supply
responds to a command to go from Output ON to OFF.
When the output is disabled, the unit is set to voltage
mode, voltage is set to zero and both current protect
and voltage limit are set to maximum. When the unit is
enabled, the pre-existing settings for voltage, current
protect and voltage limit are restored.

FIGURE 8.  MAX/MIN SETTING MENU

TABLE 4.  POWER SUPPLY BEHAVIOR WHEN OUTPUT IS SET TO OFF

LOAD TYPE

SETTING

If unit was in Voltage Mode when output OFF 

command issued.

If unit was in Current Mode when output OFF 

command issued.

ACTIVE

• Unit remains in voltage mode.
• Voltage set to zero.
• Both ± Current Protect set to maximum.
• Both ± Voltage Limit remain at maximum.

• Unit set to voltage mode.
• Voltage set to zero.
• Both ± Current Protect remain at maximum.
• Both ± Voltage Limit set to maximum.

RESISTIVE

• Unit remains in voltage mode.
• Voltage set to zero.
• Both ± Current Protect set to minimum box values.
• Both ± Voltage Limit. remain at maximum.

• Unit remains in current mode.
• Current set to zero.
• Both ± Current Protect set to minimum box values.
• Both ± Voltage Limit set to maximum,

BATTERY

• Unit set to current mode.
• Current set to zero.
• Both ± Voltage Protect. remain at maximum.
• Both ± Current Limit set to maximum.

• Unit remains in current mode,
• Current set to zero.
• Both ± Voltage Protect set to maximum.
• Both ± Current Limit remain at maximum.

VOLTAGE

SOURCE

VOLTAGE

CURRENT

0.0000 0.0000

Summary of Contents for BOP 10-200ME

Page 1: ...ing instructions including an Installation Operation Summary which includes hyperlinked references to detailed procedures but which can be printed as a handy reference The BOP 2KW MG ME Operator s Man...

Page 2: ...ering many electrochemical reactions Models with L suffix have been optimized for exceptionally low current ripple and noise and improved stability drift and temperature making them ideal for driving...

Page 3: ...th displayed voltage on LCD within 0 05 of rated maximum voltage VI ACCESSORIES See Table 3 TABLE 3 ACCESSORIES ITEM FUNCTION PART NUMBER Mating Connector Trigger Mates with Trigger port 142 0527 Kepc...

Page 4: ...4 228 1915 053119 KEPCO INC 131 38 SANFORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com FIGURE 1 BOP OUTPUT CHARACTERISTICS...

Page 5: ...Terminal Block Then connect OUT S and COM S lines from the BOP 2KW Sense Monitor Terminal Block to the load see Figure 7B using 22 AWG wire twisted pair ANALOG I O CONNECTIONS The Analog I O Port conn...

Page 6: ...load exists contacts cannot be held closed by actuator When the power supply is turned on it per forms a brief self test that includes testing the three processors analog interface and dis play and an...

Page 7: ...con figuration shown as a power up setting so the changes will not be lost when the unit is turned off APPLY EXIT applies the current changed setting without saving for power up and exits to the previ...

Page 8: ...AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com FIGURE 4 BOP 2KW SERIES POWER BOOST SECTION FRONT PANEL CONTROLS AND INDICATORS FIGURE...

Page 9: ...o incre ment or decrement the highlighted digit Pressing ADJUST while rotating adjusts the least significant digit If the output is on unit not in Standby changes made using the ADJUST control are imm...

Page 10: ...channel is determined by the MODE key in local mode which alternately selects either Voltage mode or Current mode or by SCPI com mand in digital remote mode The protection channel is determined automa...

Page 11: ...l are possible Otherwise the value entered is applied to both positive and negative protect channels NOTE The BOP can be configured to show the protection limits as either a single value that applies...

Page 12: ...loads Table 4 indicates how the power supply responds to a command to go from Output ON to OFF When the output is disabled the unit is set to voltage mode voltage is set to zero and both current prot...

Page 13: ...opened after the connections are complete and then the switch in series with the battery should be closed If the constant voltage type active electronic load is adjusted to zero before handling the p...

Page 14: ...com mands via RS 232 GPIB or LAN ports opera tion via web pages Analog Remote Operation via Analog I O port Details about Protect Limits and Software controlled limits Storing Recalling Power Supply...

Page 15: ...15 15 KEPCO INC 131 38 SANFORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com FIGURE 9 BOP 2KW OUTLINE DIMENSIONS Sheet 1 of 2 REAR VI...

Page 16: ...NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com FIGURE 10 BOP 2KW WIRING DIAGRAM DETAIL A S MON OUT OUT MON COM GND GND NET OUT MON N C OUT S COM S CO...

Reviews: