background image

SC-FI Signal Conditioner

1

Description:
The SC-FI is a two wire frequency to analog converter that
converts a pulse rate input into a 4-20 mA output signal
proportional to frequency or rate.

The input pulse rate is amplified and filtered by the input
signal conditioning circuitry. Two forms of input signal condi-
tioning are provided, one for magnetic pickups and the other
being an isolated pulse input.

The amplified frequency signal is then converted to an ana-
log  signal using a precision frequency to analog converter.

The output stage derives it’s power from the output current
loop. The output stage converts the input signal into the
desired output range. Multi-turn potentiometers provide for
the necessary trimming of span and zero.

SPECIFICATIONS:

Operating Temperature

32

°

 F (0

°

C) to 158

°

F (70

°

C)

High Level Pulse Input

Type: Opto-Isolated
Logic 1: 4-30 VDC
Logic 0: 0-1 VDC
Frequency Range: 0-10 kHz
Fault Protection:

Reverse Polarity Protection
Over Voltage Protection

Isolation Voltage: 500 V
Fast Transient Immunity: 500 V
Maximum Rise Time: No Limit
Maximum Fall Time: No Limit

Magnetic Pickup Input

Differential Input
Input Impedance: 10 k

Frequency Response: 0-3500 Hz
Trigger Sensitivity: 30 mV p-p
Over Voltage Protection: 

±

 30 VDC

Frequency to Current Conversion

Range Selection: DIP Switch Selectable
Available Ranges:

150 Hz, 300 Hz, 600 Hz, 1200 Hz,
2500 Hz, 5000 Hz, 10,000 Hz

Factory Default:

1000 Hz

Analog Output

Accuracy: 

±

 0.1% Span (@ 20

°

 C)

Output Type: Two Wire, Loop Powered
Range: 4-20 mA (10 - 50 mA optional)
Compliance Voltage: 10 to 40 VDC
Loop Burden: < 10 VDC (less than 500 

)

Trim Controls: Zero & Span, non-interacting

Span (20 mA) Trim Range: 50% to 100% of full scale

Linearity:  < 

±

0.1% Span

Output Voltage Effect: < 

±

 0.002% Span/Volt

Temperature Effect: < 200 PPM/C

°

Reverse Polarity Protected
Noise Content: < 0.2% Span
Response Time: 0.1 second (1 sec. jumper selectable)
Over-current Limiting: 35 mA
Output Loop Indicator:

LED illuminates when output loop is
powered by proper polarity and blinks
proportionally to the input frequency.

Mounting Styles

DIN Rail Mount:

Plastic enclosure with a snap fastener for
fitting to DIN 46 277 and DIN EN 50 022
assembly rails.

NEMA 4X:

4.92" x 4.92" NEMA 4X Enclosure for wall
mounting.

Explosion Proof:

Aluminum enclosure for:
Class I, Division 1, Groups B, C & D
Class II, Division I, Groups E, F & G.

Simplified Block Diagram

F/V

V ref

Span

Zero

+

mV

Input

3-30V

Input

Loop Powered

4-20mA Output

+

V/I

3.3k

10k

10k

Typical Wiring Hookup

1• Magnetic pickup

2• Magnetic pickup

3• Shield (common)

4• Opto-isolator In +

5• Opto-isolator In –

6• Shield (common)

7•

8• Output –

9• Do Not Use

REED

SWITCH
PULSER

DC

POWER

SUPPLY

ANALOG

4-20 mA

DEVICE

+

+

1• Magnetic pickup

2• Magnetic pickup

3• Shield (common)

4• Opto-isolator In +

5• Opto-isolator In –

6• Shield (common)

7•

8• Output –

9• Do Not Use

DC

POWER

SUPPLY

ANALOG

4-20 mA

DEVICE

+

+

Turbine Meter  with

Mag Pickup

Magnetic Pickup Hookup

High Level Pulse Hookup

Summary of Contents for SC-FI Series

Page 1: ...Frequency to Current Signal Conditioner SC FI Series 99483 10 9 98 KESSLER ELLIS PRODUCTS 10 Industrial Way East Eatontown NJ 07724 800 631 2165 732 935 1320 Fax 732 935 9344 http www kep com...

Page 2: ...THIS PAGE IS BLANK...

Page 3: ...SCRIPTION 1 SPECIFICATIONS 1 TYPICAL WIRING HOOKUP 1 INPUT OUTPUT SETTINGS 2 L OPTION SPECIFICATIONS 3 L OPTION TYPICAL WIRING 3 L OPTION INPUT OUTPUT SETTINGS 4 DIMENSIONS 5 WARRANTY 5 DECODING PART...

Page 4: ...THIS PAGE IS BLANK...

Page 5: ...Hz 1200 Hz 2500 Hz 5000 Hz 10 000 Hz Factory Default 1000 Hz Analog Output Accuracy 0 1 Span 20 C Output Type Two Wire Loop Powered Range 4 20 mA 10 50 mA optional Compliance Voltage 10 to 40 VDC Loop...

Page 6: ...ut 0 frequency and adjust the 4 mA pot Connect your maximum frequency and adjust the 20 mA pot FIGURE 2 1 2 3 4 5 6 7 8 9 INPUT FREQUENCY RANGE SETTINGS The appropriate range is selected by turning ON...

Page 7: ...ectable Available Ranges 30 Hz 60 Hz 120 Hz 240 Hz 480 Hz 960 Hz 1920 Hz Factory Default 100 Hz Analog Output Accuracy 0 1 Span 20 C Output Type Two Wire Loop Powered Range 4 20 mA 10 50 mA optional C...

Page 8: ...tion Input 0 frequency and adjust the 4 mA pot Connect your maximum frequency and adjust the 20 mA pot FIGURE 2 1 2 3 4 5 6 7 8 9 INPUT FREQUENCY RANGE SETTINGS The appropriate range is selected by tu...

Page 9: ...ies add to end of part number DR 4 4 DIN Rail WARRANTY This product is warranted against defects in materials and workmanship for a period of two 2 years from the date of shipment to Buyer The Warrant...

Reviews: