Cause
4-20 mA Input current at
comp input smaller than
3.5 mA:
• Faulty Wiring
• Transmitter not set to "4-20
mA"
• Transmitter defective
Input current at RTD input
too low:
• Faulty wiring
• RTD defective
Calculated pulse frequency
too large:
• Pulse width setting too long
• Larger pulse scaler needed
Current input signal of the
level input exceeds 20.5 mA:
• Sensor overranged
• Incorrect full scale setting
of level sensor
• Function error in
transmitter or faulty wiring
Current input signal of the
compensation input exceeds
20.5 mA:
• Sensor overranged
• Incorrect full scale setting
of transmitter
• Function error in
transmitter or faulty wiring
Current input signal of the
level input is smaller than
3.5 mA:
• Level sensor not set to
4-20 mA
• Function error in
transmitter or faulty wiring
13.3 Error & Warning Messages:
Remedy
• Check wiring
• Check function of
sensor
• Check wiring
• Check function of
RTD sensor
• Adjust pulse value
• Adjust pulse width
• Check process
conditions
• Check the full
scale setting of the
transmitter
• Check the
application
conditions
• Check wiring
• Check the full
scale setting of the
transmitter
• Check the
application
conditions
• Check wiring
• Check wiring
• Check calibration of
transmitter
• Check function of
transmitter
Error/Warning Message
COMP INPUT TOO LOW
RTD OUT OF RANGE
PULSE OUT OVERFLOW
LEVEL INPUT TOO HIGH
COMP INPUT TOO HIGH
LEVEL INPUT TOO LOW
13.3.1
Sensor/Process Alarms