
Remote RMX-3200 Version 5.2x Configuration Guide
Configuring Alarm Entries in the Central Alarm Table: Configuring an Alarm Entry for a Telnet Connection
that Comes Up
15-19
4. (optional) Verify that the alarm entry has been configured properly:
show alarm-entries name TelnetConnUp
The command response appears similar to the following:
5. Save the configuration.
(Dub)>show alarm-entries name TelnetConnUp
Name - TelnetConnUp
State - normal
Current Message -
Description - Telnet connection up
Nagging Interval - 0
Nagging Level - major
Trap - enabled
Raw - disabled
TL1 - disabled
TL1 AID -
TL1 Class - env
TL1 Affect - nsa
TL1 Type -
TL1NE - 1
Category -
NE Name -
Alarm Actions:
Severity Originator Trigger Message
------------------------------------------------------------------
normal telnet 192.168.0 conn-up Telnet connection no
(Dub)>
Summary of Contents for RMX-3200
Page 322: ...Remote RMX 3200 Version 5 2x Configuration Guide Drop and Continue Functionality Failover 27 6...
Page 382: ...Remote RMX 3200 Version 5 2x Configuration Guide Glossary 32...
Page 386: ...Remote RMX 3200 Version 4 1x Configuration Guide 1 4...
Page 388: ...Remote RMX 3200 Version 5 1x Configuration Guide Copyrights 2...