Kendrion Kuhnke Automation GmbH
Construction and Functionality
Econo
30
4.6.6 Serial Communication
RS-232
/ CAN1 (X8)
The system uses COM3 for access to the
RS-232
port. The
RS-232
port is not electrically insulated.
Pin wiring
X8
RS 232 Interface
Pin
Function
1
RxD
2
TxD
3
GND
4
Shield
5
Shield
The
CAN port
complies with standard ISO 11898 and supports baud rates of up to 1 Mbps. This port is
electrically insulated.
Pin wiring
X8
CAN Interface
Pin
Function
6
CAN_H
7
CAN_L
8
CAN_GND
9
CAN_H
10
CAN_L
Technical data
RS 232
Quantity
1
Signal
RS 232
Baud rate
max. 115,200 baud,
(57,600, 19,200, 9,600)
Electrical insulation
no galvanic isolation
CAN 1
Signal
RS 485
Baud rate
max. 1 Mbps,
(500, 250, 125 kbps)
Electrical insulation
galvanic isolation
Termination
attached to the connector
Connection data
X8
Mating Connector
Type
female PUSH-IN spring connector
released by push-buttons
Poles
10, two rows
Order data
Weidmüller: 1460190000
Wire cross section
min. 0.14 mm²
max. 1.5 mm²
Information
You may connect the CAN termination (wired 120
Ω resistor) directly to the pins.