background image

8  Indoor unit installation 

Kelvinator Air Conditioning

Indoor unit installation

Drain piping

1.

 Run the drain hose as shown in figure 6, ensuring it has a
constant downward fall.

2.

 The installer must supply a suitable drain hose extension to run
from the indoor unit drain hose to the desired drain location.
The drain hose extension should be fitted and sealed tightly
with the indoor unit drain hose, and secured in place with vinyl
tape. Ensure that the drain hose extension also has a continual
downward fall with an air gap at the bottom, and is drained to
a suitable location which will not cause damage to people or
property.

3.

 Remove the air filter and pour some water into the drain pan to
check the water flows smoothly.

Fig 6.

Right

Wrong

No trap is permitted

Do not put the end of 

drain hose into water

Connect the cable to the indoor unit

WARNING

caution

Electrical installation must be completed by suitably qualified 

electrician

Electric safety regulations for the initial installation

1.

 If there is serious safety problem about the power supply,
the technician should refuse to install the air conditioner and
explain to the client until the problem is solved.

2.

 Power voltage should be in the range of 90%–110%
of rated voltage.

3.

 The surge protector and main power switch with a 1.5 times
capacity of maximum. Current of the unit should be installed in
power circuit. Ensure the air conditioner is grounded well.

4.

 The appliance shall be installed in accordance with national
wiring regulations.

5.

 An all-pole disconnection device which has at least 3mm
clearances in all poles, the residual current device (RCD)
having a rated residual operating current not exceeding 30mA,
and disconnection must be incorporated in the fixed wiring
in accordance with the wiring rules. Refer to the table for
recommended circuit breaker rating for normal installation,
however national and local wiring regulations will prevail.

7.

 According to the attached electrical connection diagram

 

located on the panel of the indoor and outdoor unit to

 

connect 

the wire.

8.

 All wiring must comply with local and national electrical codes

 

and be installed by qualified and skilled electricians.

9.

 Every wire must be connected firmly. No wire should be

 

allowed to touch refrigerant tubing, the compressor, or any

 

moving parts.

10.

 Loose wiring may cause the terminal to overheat or result in

 

unit malfunction. A fire hazard may also exist. Therefore, be

 

sure all wiring is tightly connected.

11.

 This air conditioner 

will

 need to be installed on its own

 

separate 

circuit, please refer to AS/NZS 3000 and local wiring

 

regulations 

for requirements.

12.

 For this air conditioner, the main power supply is fed to the

 

outdoor unit terminal block, ensure that the main power supply

 

wires running to the outdoor unit can carry the full current
of the air conditioner, which is stated on the rating label,

 

according to national wiring regulations. The power and signal

 

cable that connects from outdoor unit to indoor unit do not

 

carry the full compressor current, therefore 1.0mm

2

 (or larger) is

 

suitable for this application.

Summary of Contents for KSV25CRH

Page 1: ...nstallation Manual KSV25CRH KSV35CRH KSV71CRH KSV25HRH KSV35HRH KSV50HRH KSV71HRH KSV90HRH KSD25HRH KSD35HRH KSD50HRH KSD71HRH KSD90HRH KSV25HWH KSV35HWH KSV50HWH KSV71HWH KSV90HWH KSD25HWH KSD35HWH K...

Page 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Page 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Page 4: ...room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu oor ar...

Page 5: ...T3 9x25 5 Remote control Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use b...

Page 6: ...d with the machine differ from appliance to appliance Dimensions are in mm unless otherwise stated 232 219 581 300 53 5 76 53 5 335 232 128 192 802 1080 297 43 43 43 65 75 65 75 Left rear side refrige...

Page 7: ...ft side drainage connection The connection of the drain pipe hose must be connected by a qua d installer in accordance with these instructions to prevent leakage 3 Attach the drain hose to the undersi...

Page 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resid...

Page 9: ...e end of the connection cable fully inserting into the terminal block Tighten the terminal block screws then gently pull on the wires to con hey are securely attached 6 Fasten the connection cable wit...

Page 10: ...and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensions B mm 885 x 554 x 365 32 5 514 340 924 x 702 x...

Page 11: ...the standard 5m then add additional refrigerant according to the below table which also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also re...

Page 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper p...

Page 13: ...hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is off 2 Confirm t...

Page 14: ...ic ring INDOOR UNIT POWER SUPPLY S 2 N L N 1 L Y G INDOOR UNIT POWER SUPPLY Please note that different models are supplied with a different combination of magnetic rings that must be installed by a li...

Page 15: ...e Pipe length and refrigerant amount Additional refrigerant required for pipe length greater than Minimum length 3m standard 5m installation can be calculated using the following equation M L 5 x A Wh...

Page 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Page 17: ...re are no gas leaks follow the below steps to complete an operation test Check that all tubing and wiring have been properly connected Check that the gas and liquid side service valves are fully open...

Page 18: ...sks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of v...

Page 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Page 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Page 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Page 22: ...22 Notes Kelvinator Air Conditioning Notes...

Page 23: ...Kelvinator Air Conditioning Warranty 23...

Page 24: ...ND phone 0800 436 245 fax 0800 225 088 email customercare electrolux co nz web kelvinator co nz For more information on all Kelvinator appliances or for dimension and installation information call int...

Reviews: