Kelvinator KSV25CRH Installation Manual Download Page 16

16  Outdoor unit installation 

Kelvinator Air Conditioning

Outdoor unit installation

 

 Make sure the refrigerant added into the air conditioner is 

liquid

 form. 

Caution in handling the service valve

 

 To open the service valve, remove the cap then open the valve 
stem using an Allen key until it hits the stopper, do not try to 
open it further.

 

 To close the service valve, securely tighten the valve stem 
using an Allen key, then fit and tighten the cap with a spanner.

When Using the Vacuum Pump 

(For method of using a manifold valve, refer to its operation 
manual.) 

1.   Completely tighten the flare nuts, A, B, C, D, connect the 

manifold valve charge hose to a charge port of the  
low-pressure valve on the gas pipe side. 

2.   Connect the charge hose connection to the vacuum pump. 

3.  Fully open the handle Lo of the manifold valve. 

4.   Operate the vacuum pump to evacuate. After starting 

evacuation, slightly loose the flare nut of the Lo valve on the 
gas pipe side and check that the air is entering (Operation 
noise of the vacuum pump changes and a compound meter 
indicates 0 instead of minus). Then retighten the flare nut.

5.   Keep the vacuum pump running for more than 15 minutes and 

make sure the pressure reading is -76cm.Hg or lower. Now 
fully close the low handle of the manifold valve and stop the 
operation of the vacuum pump. 

6.   Turn the stem of the packed valve B about 45 counterclockwise 

for 6–7 seconds after the gas coming out, then tighten the 
flare nut again. Make sure the pressure display in the pressure 
indicator is a little higher than the atmosphere pressure. 

7.   Remove the charge hose from the Low pressure charge hose.

8.   Fully open the service valve stems B and A. 

9.  Securely tighten the cap of the service valve. 

Indoor

unit

Refrigerant

Outdoor

unit

Service valve

Flare nut

Stopper

Cap

Valve body

Manifold valve

Pressure gauge

Compound meter

-76cmHg

Handle Lo

Charge hose

Low pressure valve

Vacuum pump

Charge hose

Handle Hi

Half union

B. High pressure valve 

(2-way) - liquid side

D

Liquid side

Gas side

A. Low pressure 

valve (3-way) - 

gas side.

C

Fig. 20

Fig. 21

Valve stem

Summary of Contents for KSV25CRH

Page 1: ...nstallation Manual KSV25CRH KSV35CRH KSV71CRH KSV25HRH KSV35HRH KSV50HRH KSV71HRH KSV90HRH KSD25HRH KSD35HRH KSD50HRH KSD71HRH KSD90HRH KSV25HWH KSV35HWH KSV50HWH KSV71HWH KSV90HWH KSD25HWH KSD35HWH K...

Page 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Page 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Page 4: ...room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu oor ar...

Page 5: ...T3 9x25 5 Remote control Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use b...

Page 6: ...d with the machine differ from appliance to appliance Dimensions are in mm unless otherwise stated 232 219 581 300 53 5 76 53 5 335 232 128 192 802 1080 297 43 43 43 65 75 65 75 Left rear side refrige...

Page 7: ...ft side drainage connection The connection of the drain pipe hose must be connected by a qua d installer in accordance with these instructions to prevent leakage 3 Attach the drain hose to the undersi...

Page 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resid...

Page 9: ...e end of the connection cable fully inserting into the terminal block Tighten the terminal block screws then gently pull on the wires to con hey are securely attached 6 Fasten the connection cable wit...

Page 10: ...and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensions B mm 885 x 554 x 365 32 5 514 340 924 x 702 x...

Page 11: ...the standard 5m then add additional refrigerant according to the below table which also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also re...

Page 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper p...

Page 13: ...hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is off 2 Confirm t...

Page 14: ...ic ring INDOOR UNIT POWER SUPPLY S 2 N L N 1 L Y G INDOOR UNIT POWER SUPPLY Please note that different models are supplied with a different combination of magnetic rings that must be installed by a li...

Page 15: ...e Pipe length and refrigerant amount Additional refrigerant required for pipe length greater than Minimum length 3m standard 5m installation can be calculated using the following equation M L 5 x A Wh...

Page 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Page 17: ...re are no gas leaks follow the below steps to complete an operation test Check that all tubing and wiring have been properly connected Check that the gas and liquid side service valves are fully open...

Page 18: ...sks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of v...

Page 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Page 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Page 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Page 22: ...22 Notes Kelvinator Air Conditioning Notes...

Page 23: ...Kelvinator Air Conditioning Warranty 23...

Page 24: ...ND phone 0800 436 245 fax 0800 225 088 email customercare electrolux co nz web kelvinator co nz For more information on all Kelvinator appliances or for dimension and installation information call int...

Reviews: