Kelvinator KSV25CRH Installation Manual Download Page 12

12  Outdoor unit installation 

Kelvinator Air Conditioning

Flaring work

TIPS & INFORMATION

 important

For installer 

It is critical that the installer follows the correct flaring procedure 

using the right tools to produce good quality flares in order to 

ensure installation without refrigerant gas leaks. 

Service calls caused by poor installation are the responsibility of 

the installer, and these service calls will be referred back to the 

installer accordingly. 

Please take care to make the flare connection carefully and test for 
refrigerant leaks before commissioning the air conditioner.

Main cause for refrigerant leakage is due to defect in the flaring 
work. Carry out correct flaring work using the following procedure:

Cut the pipes and the cable

1.

 Purchase the appropriate pipe size locally according to the
table on page 11.

2.

 Measure the distance between the indoor and the
outdoor unit.

3.

Cut the pipes a little longer than the measured distance.

4.

Cut the cable 1.5m longer than the pipe length.

5.

Cut pipes must follow the requirements shown in figure 12.

Burr removal

1.

 Completely remove all burrs from the cut cross section
of the pipe.

2.

 Put the end of the copper pipe in a downward direction as you
remove burrs in order to avoid dropping burrs into
the the pipe, as shown in figure 13.

WARNING

caution

Putting nut on

Remove flare nuts attached to indoor and outdoor unit, then put 
them on pipe/tube having completed burr removal (not possible to 
put them on after flaring work).

Flaring work

Carry out flaring work using a flaring tool as shown in figure 15, and 

ensure dimension A is maintained within the tolerance as indicated 

in the table below.

Outer diameter (mm)

Dimension A (mm) as per  g. 15

Max.

Min.

ø 6.35 (1/4") 

1.3

0.7

ø 9.52 (3/8") 

1.6

1.0

ø 12.7 (1/2") 

1.8

1.0

ø 15.9 (5/8") 

2.4

2.2

"

90°

Oblique

Fig. 12

Fig. 13

Fig. 14

Point down

Copper tube

Flare nut

Pipe

Reamer

Roughness

Burr

Checking flare work

Compare the flare work with the adjacent diagram. If the pipe has 
any defect, cut off the flared section and redo the flare until it meets 
the requirements.

Fig. 15 

Bar

Copper 

pipe

Clamp 

handle

Bar

Handle

Yoke

Cone

Red arrow mark

A

Outdoor unit installation

Summary of Contents for KSV25CRH

Page 1: ...nstallation Manual KSV25CRH KSV35CRH KSV71CRH KSV25HRH KSV35HRH KSV50HRH KSV71HRH KSV90HRH KSD25HRH KSD35HRH KSD50HRH KSD71HRH KSD90HRH KSV25HWH KSV35HWH KSV50HWH KSV71HWH KSV90HWH KSD25HWH KSD35HWH K...

Page 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Page 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Page 4: ...room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu oor ar...

Page 5: ...T3 9x25 5 Remote control Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use b...

Page 6: ...d with the machine differ from appliance to appliance Dimensions are in mm unless otherwise stated 232 219 581 300 53 5 76 53 5 335 232 128 192 802 1080 297 43 43 43 65 75 65 75 Left rear side refrige...

Page 7: ...ft side drainage connection The connection of the drain pipe hose must be connected by a qua d installer in accordance with these instructions to prevent leakage 3 Attach the drain hose to the undersi...

Page 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resid...

Page 9: ...e end of the connection cable fully inserting into the terminal block Tighten the terminal block screws then gently pull on the wires to con hey are securely attached 6 Fasten the connection cable wit...

Page 10: ...and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensions B mm 885 x 554 x 365 32 5 514 340 924 x 702 x...

Page 11: ...the standard 5m then add additional refrigerant according to the below table which also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also re...

Page 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper p...

Page 13: ...hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is off 2 Confirm t...

Page 14: ...ic ring INDOOR UNIT POWER SUPPLY S 2 N L N 1 L Y G INDOOR UNIT POWER SUPPLY Please note that different models are supplied with a different combination of magnetic rings that must be installed by a li...

Page 15: ...e Pipe length and refrigerant amount Additional refrigerant required for pipe length greater than Minimum length 3m standard 5m installation can be calculated using the following equation M L 5 x A Wh...

Page 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Page 17: ...re are no gas leaks follow the below steps to complete an operation test Check that all tubing and wiring have been properly connected Check that the gas and liquid side service valves are fully open...

Page 18: ...sks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of v...

Page 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Page 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Page 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Page 22: ...22 Notes Kelvinator Air Conditioning Notes...

Page 23: ...Kelvinator Air Conditioning Warranty 23...

Page 24: ...ND phone 0800 436 245 fax 0800 225 088 email customercare electrolux co nz web kelvinator co nz For more information on all Kelvinator appliances or for dimension and installation information call int...

Reviews: