Kelvinator KSV25CRH Installation Manual Download Page 13

Kelvinator Air Conditioning

 Outdoor unit installation  13

Outdoor unit installation

Tightening Connection

 Align the center of the pipes.

 Sufficiently tighten the flare nut with fingers, and then tighten it
with a spanner and torque wrench as shown in Fig.16 & 17.

Outer diameter (mm)

ø 6.35 (1/4")

15-20

ø 9.52 (3/8")

35-40

ø 12.7 (1/2")

50-55

ø 15.9 (5/8")

60-65

Torque (Nm)

WARNING

caution

 Excessive torque can break the nut or flared pipe and cause
a leak, and too low torque can also cause a leak. Follow the
specified torque and use a torque wrench as required.

 When flared joints are reused, the flare part shall be
re-fabricated.

 Neatly run the refrigeration pipe from the indoor unit
connection to the outdoor unit suction and discharge
connections. Follow the same flaring procedure outlined
above to flare and connect the suction and discharge pipes to
the outdoor unit accordingly.

Insulating the pipes

Wrap suitable insulation material (supplied by the installer) separately 
around each individual refrigeration pipe, the suction and discharge 
pipes must not be in direct contact. Ensure that the flare connections 
are covered, then wrap the insulated pipes with vinyl tape. 

Attach the interconnecting electrical cable and drain pipe to 
the pipe assembly with narrow vinyl tape, then wrap the whole 
assembly with wide vinyl tape starting from top to bottom, as 
pictured in the diagram below.

Finally plug the hole in the wall using gum type sealer.

Indoor unit tubing

Flare nut

Pipings

Fig. 16

Fig. 17

Outdoor unit electrical connection

1.

 Check that power supply to the air conditioner circuit is off

2.

 Confirm that power cable with suitable rating for the air
conditioner current rating has been run from the circuit breaker
to the isolation switch, according to AS/NZS 3000 & local
wiring rules.

3.

 Run power supply cable from the isolation switch to the
outdoor unit terminal block area. Also run the interconnecting
cables from the indoor unit to the outdoor unit terminal
block area. All exposed power cables must be protected, for
example in conduit.

4.

 Remove the terminal block cover and loosen the cable clamp
as shown in figure 18.

Terminal block

Cover

Screw (1–2 model 

dependant)

Cable clamp

Fig. 18

5.

 

Connect the interconnecting cable from the indoor unit to the 
terminal block following the wiring diagram provided on the 
following page

, ensuring

 

that the colours match between 

indoor unit and outdoor unit.

6.

 Connect the main power supply cables from the isolation

 

switch to the outdoor unit terminal block following the wiring

 

diagram.

7.

 Ensure that the terminal block screws are secure by gently

 

pulling the wires.

8.

 Fit the cable clamp over the incoming wires to protect from

 

strain, then fit the cover and fix in place with the screw.

suction line pipe

liquid line pipe

connection pipe

wrap with vinyl tape

indoor pipe unit

pipe

vinyl tape

(narrow) 

wrap with vinyl

tape (wide)

pipe

vinyl tape (wide)

connection 

cable

vinyl tape  

(narrow)

drain hose

connection

power cable

incorrect

heat insulation

Summary of Contents for KSV25CRH

Page 1: ...nstallation Manual KSV25CRH KSV35CRH KSV71CRH KSV25HRH KSV35HRH KSV50HRH KSV71HRH KSV90HRH KSD25HRH KSD35HRH KSD50HRH KSD71HRH KSD90HRH KSV25HWH KSV35HWH KSV50HWH KSV71HWH KSV90HWH KSD25HWH KSD35HWH K...

Page 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Page 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Page 4: ...room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu oor ar...

Page 5: ...T3 9x25 5 Remote control Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use b...

Page 6: ...d with the machine differ from appliance to appliance Dimensions are in mm unless otherwise stated 232 219 581 300 53 5 76 53 5 335 232 128 192 802 1080 297 43 43 43 65 75 65 75 Left rear side refrige...

Page 7: ...ft side drainage connection The connection of the drain pipe hose must be connected by a qua d installer in accordance with these instructions to prevent leakage 3 Attach the drain hose to the undersi...

Page 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resid...

Page 9: ...e end of the connection cable fully inserting into the terminal block Tighten the terminal block screws then gently pull on the wires to con hey are securely attached 6 Fasten the connection cable wit...

Page 10: ...and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensions B mm 885 x 554 x 365 32 5 514 340 924 x 702 x...

Page 11: ...the standard 5m then add additional refrigerant according to the below table which also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also re...

Page 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper p...

Page 13: ...hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is off 2 Confirm t...

Page 14: ...ic ring INDOOR UNIT POWER SUPPLY S 2 N L N 1 L Y G INDOOR UNIT POWER SUPPLY Please note that different models are supplied with a different combination of magnetic rings that must be installed by a li...

Page 15: ...e Pipe length and refrigerant amount Additional refrigerant required for pipe length greater than Minimum length 3m standard 5m installation can be calculated using the following equation M L 5 x A Wh...

Page 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Page 17: ...re are no gas leaks follow the below steps to complete an operation test Check that all tubing and wiring have been properly connected Check that the gas and liquid side service valves are fully open...

Page 18: ...sks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of v...

Page 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Page 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Page 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Page 22: ...22 Notes Kelvinator Air Conditioning Notes...

Page 23: ...Kelvinator Air Conditioning Warranty 23...

Page 24: ...ND phone 0800 436 245 fax 0800 225 088 email customercare electrolux co nz web kelvinator co nz For more information on all Kelvinator appliances or for dimension and installation information call int...

Reviews: