background image

20  Information servicing 

Kelvinator Air Conditioning

Information servicing

Charging procedures 

In addition to conventional charging procedures, the following 
requirements shall be followed: 

• 

 Ensure that contamination of different refrigerants does not 
occur when using charging equipment. Hoses or lines shall 
be as short as possible to minimize the amount of refrigerant 
contained in them. 

• 

 Cylinders shall be kept upright. 

• 

 Ensure that the refrigeration system is earthed prior to 
charging the system with refrigerant. 

• 

 Label the system when charging is complete (if not already). 

• 

 Extreme care shall be taken not to overfill the refrigeration 
system. 

• 

 Prior to recharging the system it shall be pressure tested 
with OFN. The system shall be leak tested on completion of 
charging but prior to commissioning. A follow up leak test shall 
be carried out prior to leaving the site.

Decommissioning

Before carrying out this procedure, it is essential that the technician 
is completely familiar with the equipment and all its detail. It is 
recommended good practice that all refrigerants are recovered 
safely. Prior to the task being carried out, an oil and refrigerant 
sample shall be taken.

In case analysis is required prior to re-use of reclaimed refrigerant. 
It is essential that electrical power is available before the task is 
commenced. 

a)  Become familiar with the equipment and its operation. 

b)  Isolate system electrically. 

c)  Before attempting the procedure ensure that: 

 

• 

 Mechanical handling equipment is available, if required, 
for handling refrigerant cylinders; 

 

• 

 All personal protective equipment is available and being 
used correctly; the recovery process is supervised at 

 

• 

 All times by a competent person; 

 

• 

 Recovery equipment and cylinders conform to the 
appropriate standards. 

d)   Pump down refrigerant system, if possible. 

e)   If a vacuum is not possible, make a manifold so that refrigerant 

can be removed from various parts of the system. 

f) 

 Make sure that cylinder is situated on the scales before 
recovery takes place. 

g)   Start the recovery machine and operate in accordance with 

manufacturer's instructions. 

h)   Do not overfill cylinders. (No more than 80 % volume liquid 

charge). 

i) 

 Do not exceed the maximum working pressure of the cylinder, 
even temporarily. 

j) 

 When the cylinders have been filled correctly and the process 
completed, make sure that the cylinders and the equipment 
are removed from site promptly and all isolation valves on the 
equipment are closed off. 

k)   Recovered refrigerant shall not be charged into another 

refrigeration system unless it has been cleaned and checked. 

Labelling

Equipment shall be labelled stating that it has been  
de-commissioned and emptied of refrigerant. The label shall be 
dated and signed. Ensure that there are labels on the equipment 
stating the equipment contains flammable refrigerant.

Recovery

• 

 When removing refrigerant from a system, either for servicing 
or decommissioning, it is recommended good practice that all 
refrigerants are removed safely.

• 

 When transferring refrigerant into cylinders, ensure that only 
appropriate refrigerant recovery cylinders are employed. 
Ensure that the correct numbers of cylinders for holding the 
total system charge are available. All cylinders to be used are 
designated for the recovered refrigerant and labelled for that 
refrigerant (i.e. special cylinders for the recovery of refrigerant). 
Cylinders shall be complete with pressure relief valve and 
associated shut-off valves in good working order.

• 

 Empty recovery cylinders are evacuated and, if possible, 
cooled before recovery occurs.

• 

 The recovery equipment shall be in good working order with 
a set of instructions concerning the equipment that is at hand 
and shall be suitable for the recovery inflammable refrigerants. 
In addition, a set of calibrated weighing scales shall be 
available and in good working order.

• 

 Hoses shall be complete with leak-free disconnect couplings 
and in good condition. Before using the recovery machine, 
check that it is in satisfactory working order, has been properly 
maintained and that any associated electrical components are 
sealed to prevent ignition in the event of a refrigerant release. 
Consult manufacturer if in doubt.

• 

 The recovered refrigerant shall be returned to the refrigerant 
supplier in the correct recovery cylinder, and the relevant 
Waste Transfer Note arranged. Do not mix refrigerants in 
recovery units and especially not in cylinders. If compressors 
or compressor oils are to be removed, ensure that they have 
been evacuated to an acceptable level to make certain that 
flammable refrigerant does not remain within the lubricant. 
The evacuation process shall be carried out prior to returning 
the compressor to the suppliers. Only electric heating to the 
compressor body shall be employed to accelerate this process. 
When oil is drained from a system, it shall be carried out safely.

Transportation, marking and storage for units

1.   Transport of equipment containing flammable refrigerants 

compliance with the transport regulations.

2.   Marking of equipment using signs compliance with local 

regulations.

3.   Disposal of equipment using flammable refrigerants 

Compliance with national regulations.

4.   Storage of equipment/appliances The storage of equipment 

should be in accordance with the manufacturers instructions.

5.   Storage of packed (unsold) equipment  

Storage package protection should be constructed such that 
mechanical damage to the equipment inside the package 
will not cause a leak of the refrigerant charge. The maximum 
number of pieces of equipment permitted to be stored 
together will be determined by local regulations.

Summary of Contents for KSD25HRG

Page 1: ...Inverter Air Conditioner Installation Manual KSV25CRG KSV35CRG KSV70CRG KSV25HRG KSD25HRG KSV35HRG KSD35HRG KSV50HRG KSD50HRG KSV70HRG KSD70HRG KSV80HRG KSD80HRG ...

Page 2: ...s air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information on disposal for users Most of the packing materials are recyclable Please dispose of those materials through your local recycling depot or by placing them in appropriate collection containers If you ...

Page 3: ...responsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnected Please read this installation manual and the user manual before installation and carefully store in a handy place for later reference Inside you will find many helpful hints on how to install and ...

Page 4: ...minimum room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimum floor area for the installation Outdoor unit If an awning is built over the unit to prevent direct sunlight or rain be careful that heat radiation from the condenser is not obstructed Do not instal...

Page 5: ...ol Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use block bases for outdoor unit Adjust its height until the unit is leveled Otherwise water leakage or pooling of water may occur Where there is a danger of the unit falling use foot bolts to fix Allow two of A B and C directi...

Page 6: ...e appropriate wall fixings suitable for the wall type being fixed to which is sufficient to support the full weight of the indoor unit 3 Secure the installation plate to the wall with screws NOTE Mount the installation plate and drill holes in the wall according to the wall structure and corresponding mounting points on the installation plate The installation plate provided with the machine differ...

Page 7: ... to drain from both sides another drain pipe will need to be supplied by the installer If choosing one side drainage connection make sure the drain hole on the other side is well plugged For 2 5kW 3 5kW models if choosing left hand or left back piping please choosing left side drainage connection The connection of the drain pipe hose must be connected by a qualified installer in accordance with th...

Page 8: ...e shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated residual operating current not exceeding 30mA and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules Refer to the table for recommended circuit breaker rating for ...

Page 9: ...clamp Match wire colours with terminal numbers on indoor and outdoor unit terminal blocks and firmly screw wires to the corresponding terminals It is recommended to use the following wire colour sequence 1 L Brown 2 N Blue S White Earth Yellow Green 5 Connect the end of the connection cable fully inserting into the terminal block Tighten the terminal block screws then gently pull on the wires to c...

Page 10: ...hor the outdoor unit with a 8 or 10 diameter bolt and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensions B mm KSV25CRG KSV25HRG KSD25HRG KSV35CRG KSV35HRG KSD35HRG 885 x 554 x 365 35 514 340 KSV50HRG KSD50HRG 924 x 702 x 382 44 540 350 KSV70CRG KSV70HRG KSD70HRG 924 x 702 x 382 55 540 350 KSV80HRG K...

Page 11: ...ximum pipe length and maximum height difference between indoor and outdoor units Please also refer to the below table for discharge and suction pipe diameter Model Discharge pipe diameter Suction pipe diameter Standard length m Maximum length m Maximum height m Additonal refrigerant g m KSV25CRG ø 6 35 1 4 ø 9 52 3 8 5 25 10 15 KSV35CRG ø 6 35 1 4 ø 12 7 1 2 5 25 10 15 KSV70CRG ø 9 52 3 8 ø 15 9 5...

Page 12: ...ger than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the the pipe as shown in figure 13 WARNING caution Putting nut on Remove flare nuts attached to indoor and outdoor uni...

Page 13: ...w Finally plug the hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is off 2 Confirm that power cable with suitable rating for the air conditioner current rating has been run from the circuit breaker to the isolation switch according to AS NZS 3000 local wiring rules...

Page 14: ...click is heard to confirm it has locked into place Secure the demand response cable in the cable clamp then fit the terminal block cover and secure with screws Outdoor unit installation Magnetic ring installation Please note that the following models are supplied with two additional magnetic rings KSV50HRG KSD50HRG These magnetic rings must be installed in the outdoor unit terminal block area with...

Page 15: ... refrigerant g m KSV25CRG ø 6 35 1 4 ø 9 52 3 8 5 25 10 15 KSV35CRG ø 6 35 1 4 ø 12 7 1 2 5 25 10 15 KSV70CRG ø 9 52 3 8 ø 15 9 5 8 5 50 25 30 KSV25HRG ø 6 35 1 4 ø 9 52 3 8 5 25 10 15 KSV35HRG ø 6 35 1 4 ø 12 7 1 2 5 25 10 15 KSV50HRG ø 6 35 1 4 ø 12 7 1 2 5 30 20 15 KSV70HRG ø 9 52 3 8 ø 15 9 5 8 5 50 25 30 KSV80HRG ø 9 52 3 8 ø 15 9 5 8 5 50 25 30 KSD25HRG ø 6 35 1 4 ø 9 52 3 8 5 25 10 15 KSD35...

Page 16: ...gas pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running for more than 15 minutes and make sure the pressure reading is 76cm Hg or lower Now fully close the low handle of the manifold valve and stop the operation of the vacuum pump 6 Turn the stem of the ...

Page 17: ...Cover Outdoor unit check point B D C A Fig 22 Operation test After confirming the electrical safety has passed and confirmed there are no gas leaks follow the below steps to complete an operation test Check that all tubing and wiring have been properly connected Check that the gas and liquid side service valves are fully open 1 Connect the power press the ON OFF button on the remote controller to ...

Page 18: ...risks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of ventilation shall continue during the period that the work is carried out The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere Checks...

Page 19: ...ble for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection equipment shall be calibrated in a refrigerant free area Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used Leak detection equipment shall be set a...

Page 20: ...be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommissioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed E...

Page 21: ...Kelvinator Air Conditioning Notes 21 Notes ...

Page 22: ...22 Notes Kelvinator Air Conditioning Notes ...

Page 23: ...ty unless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii misuse or abuse including failure to properly maintain or service iii normal wear and tear iv power surges electrical storm damage or incorrect power supply v incomplete or improper installation vi ...

Page 24: ...or appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web kelvinator com au Kelvinator We are part of the Electrolux Family To add a touch of professional inspiration to your home visit electrolux com au ...

Reviews: