15

Dialing Operation 

Whenever an event code is transferred to the SIA transmitter, either by a change of status of any 
monitored condition, or for a daily test or manual test, the transmitter initiates the dialing operation. 

 
Line Seizure 

To comply with industry standards, the Keltron S/FDACT is equipped with line seizure. Any time the 
S/FDACT needs to communicate with the receiving station, it will not be possible to use any telephone 
devices that are on the same line as the S/FDACT. Normally, this condition will last less than one minute, 
but under adverse telephone circuit conditions, could last as long as 15 minutes. Line seizure requires a 
connection to an RJ31X jack and the S/FDACT must be upstream, i.e. the first device on the incoming 
telephone line. 
 
To begin the dialing operation, the S/FDACT seizes telephone line #1. It will wait sufficient time for the 
telephone network to terminate any call that may have been in progress. The S/FDACT then goes off-
hook and blind dials the telephone number of the primary receiving station DACR, i.e. the S/FDACT will 
pause sufficient time to receive a dial tone but does not require a dial tone to start dialing.

 

 
The S/FDACT always dials using dual-tone multi-frequency (DTMF) tones. Please consult the factory for 
pulse or rotary dialing applications. 
 

Sequence of Telephone Call Attempts. 

Assuming no call attempts are successful, the Keltron S/FDACT will try a total of eight  times to 
complete a call to the central receiving station. The S/FDACT will first try two attempts to the primary 
telephone number using telephone line #1. Then the S/FDACT will try two attempts to the primary 
telephone number using telephone line #2. At this point a comm #1 trouble is indicated, i.e. a 
communication failure to the primary receiving station telephone number. Then the S/FDACT will try 
two attempts  to the secondary telephone number using telephone line #1. Finally, the S/FDACT will try 
two attempts to the secondary telephone number using telephone line #2. At this point a comm #2 trouble 
is indicated, and each status change condition that has been attempted the maximum eight times to the 
primary and secondary receiving station telephone numbers is discarded. Subsequent status change 
conditions will restart the call attempt sequence. 
 

 

Summary of Contents for SDACT

Page 1: ...User s Manual for Keltron SDACT and FDACT Fire Dialers Keltron Corporation 101A First Avenue Waltham MA 02451 Voice 781 894 8710 fax 781 899 9652 SFDACT DOC Rev 2 2 11 1 06 626 2104 P N 92MSDACT...

Page 2: ......

Page 3: ...allation Overview 19 Selecting a Location 19 Wall Mounting 19 Field Wiring Power Supply Connections 20 Field Wiring Supervised Hardwired Alarm Zones 22 Field Wiring Power Monitor Zones 23 Field Wiring...

Page 4: ......

Page 5: ...is operating properly and can successfully report an alarm the fire dialer must be tested immediately after installation and periodically thereafter according NFPA 72 Chapter 10 and the enclosed test...

Page 6: ......

Page 7: ...nals such as fire trouble water flow or supervisory can be reliably transmitted These signals are typically provided by the general alarm general trouble etc relay contact outputs of the FACP In addit...

Page 8: ...m and general trouble contact outputs The alarm output indicates serial port derived events that are pending transmission and input zone activations The trouble output indicates telephone line faults...

Page 9: ...ble and alarm with 24 hour trouble resound Line seizure is provided for use with shared phone lines as allowed by the local authority having jurisdiction A manual test button is included A silence pus...

Page 10: ...or products approved after July 23 2001 the REN for this product is part of the product identifier that has the format US AAAEQ TXXXX The digits represented by are the REN without a decimal point e g...

Page 11: ...alarm zone inputs is required for UL Listed installations remotely monitoring FACP S via the Public Switched Telephone Network To indicate the supplementary and or redundant nature of the serial data...

Page 12: ...CTBX Listed Signaling Device Enclosure 4 10K EOL resistors P N 64K3355 10K 2 Modular patch cords P N 63RJ4507 1 Programming utility CD P N SDSFDPrgmr 1 Printed user manual P N 92MSDACT For SDACT only...

Page 13: ...with conduit knockouts Hinged front access door with key lock all keyed alike Size 14 H x 17 W x 4 D Weight 12 lbs Environmental specifications Relative humidity 0 to 93 non condensing Operating tempe...

Page 14: ...zone status 4 red 4 yellow 2 Serial port status 1 red 1 yellow 4 Telephone line status 2 red 2 yellow 2 Relay output status red Audible 92 DB pulsed for alarm steady for trouble User pushbuttons 4 re...

Page 15: ...larm relay energizes and the alarm contact active LED illuminates The audible device sounds the pulsed alarm signal The corresponding event code See appendix A is transferred to the SIA transmitter se...

Page 16: ...eration If User Jumper J8 is installed then an off normal status change on the AC failure zone 5 will illuminate the power fault LED but the trouble relay local audible and the AC Power Failure transm...

Page 17: ...ne line fault is detected The Telco fault LED for that line illuminates The common trouble relay energizes and the trouble contact active LED illuminates The audible device sounds the steady trouble s...

Page 18: ...le in 24 hours if the trouble condition is still present Configuration Trouble The Keltron S FDACT stores user programmable settings in non volatile EEPROM memory The content of this memory is checked...

Page 19: ...ow battery zone 6 or no missing battery zone 7 power monitor zone inputs If all of the power monitor zones are normal the power fault LED goes out If no other monitored conditions require the common t...

Page 20: ...transmitter where is 1 for the primary telephone number and 2 for the secondary telephone number see dialing operation Daily Test Operation If the Keltron S FDACT is configured for 24 hour daily test...

Page 21: ...ion DACR i e the S FDACT will pause sufficient time to receive a dial tone but does not require a dial tone to start dialing The S FDACT always dials using dual tone multi frequency DTMF tones Please...

Page 22: ...nnect the FACP and connect the serial port to his PC or laptop While in programming mode the red and yellow serial port LEDS will alternately light once a second as an indication that programming mode...

Page 23: ...ort SDACT only J4 should be set appropriately for the specific FACP being monitored See Serial Port Installation notes J5 J6 and J7 set the normal condition of the power monitor zones 5 6 and 7 respec...

Page 24: ...18...

Page 25: ...ecting a Location The Keltron S FDACT may be installed in any environment which would be comfortable for a human being Typically the S FDACT will be installed in the same room as the FACP which it is...

Page 26: ...must include the S FDACT load current in the FACP s battery calculations Connect the 24 VDC supply making sure to observe the correct polarity Connect the positive lead to terminal 15 Connect the retu...

Page 27: ...the PSU SPSU terminal TB1 3 or TB1 4 Using the Edwards System Technology EST2 Aux Power Output The EST2 s 24 VDC non resettable auxiliary power circuit is compatible with the S FDACT Connect S FDACT t...

Page 28: ...llel at the monitored device Four EOLRs are provided for this purpose Keltron part number 64K3355 10K Connections to the alarm zones are as shown above Input zones are sampled every 62mS Changes must...

Page 29: ...zones 5 6 and 7 may be used as external power source monitor input circuits Each zone is independently configurable for either normally open or normally closed dry contact programmable activation The...

Page 30: ...lephone Line Connection The Keltron SDACT and FDACT are alarm dialing equipment and must be able to seize the telephone line and place a call in an emergency situation They must be able to do this eve...

Page 31: ...07 Plug one end of the modular cord into the S FDACT RJ 45 jack Plug the other end into the RJ31X jack For reference proper wiring of the RJ31X jack is shown in the figure below The S FDACT is electri...

Page 32: ...S or CTS set by J1 and J2 8 CTS or RTS set by J1 and J2 9 No connection IMPORTANT The FACP serial data connections provide supplementary alarm information only Use of the hardwired alarm zone inputs i...

Page 33: ...ions connect the S FDACT Trouble Relay contacts to the 7100 panel by means of an FCI AMM 2 Monitor Module or equivalent The AMM 2 is an addressable dry contact monitoring module compatible with the 71...

Page 34: ...rd electrical box adjacent to the S FDACT enclosure Connect the S FDACT Trouble Relay Normally Open contact terminal 22 to the AMM 2 violet wire Connect the S FDACT Trouble Relay Common contact termin...

Page 35: ...CT when transmitting EST2 events Local Trouble Annunciation For on premises annunciation of S FDACT trouble conditions connect the S FDACT Trouble Relay contacts to the EST2 panel by means of a Signat...

Page 36: ...hen transmitting MIR2 events Local Trouble Annunciation For on premises annunciation of S FDACT trouble conditions connect the S FDACT Trouble Relay contacts to the MIR2 panel by means of a Signature...

Page 37: ...31 SDACT Field Wiring Connection Diagram...

Page 38: ...32...

Page 39: ...o delay 1 3 hours The S FDACT programmer is a Windows PC application SFDPrgmr exe to configure an SDACT or FDACT for use The S FDACT programmer is compatible with Windows XP Windows 2000 Windows NT an...

Page 40: ...Trouble Restore Power Monitor Tab As shown in the figure below the power monitor tab is used to set the event codes for the three unsupervised power monitor zones The AC power monitor input zone 5 has...

Page 41: ...manual test Set Telephone Numbers These boxes are used to set the primary and secondary telephone numbers that S FDACT will dial when reporting Both must be set before uploading the configuration to t...

Page 42: ...Set Options Telephone Lines Used The default setting is for S FDACT to use and supervise both of its telephone line connections If a second telephone line is not available checking the line 1 only opt...

Page 43: ...sync time mode and any values you entered for the date and time will be overwritten by current values from your PC s clock Set Date and Set Time Use these boxes to manually set the date and time to be...

Page 44: ...en a previously saved S FDACT configuration file Save Saves the current configuration settings to the previously opened file If no file was opened previously it displays a standard Windows file save a...

Page 45: ...8 After the S FDACT has reported the zone restore to normal the S FDACT should return to the idle all normal state Troubleshooting In case of trouble Check for the proper power input with sufficient v...

Page 46: ...n Corporation 101A First Avenue Waltham Massachusetts 02451 Telephone 781 894 8710 Toll Free 800 966 6123 FAX 781 899 9652 Email info keltroncorp com GENERAL Telephone 781 894 8710 Email info keltronc...

Page 47: ...improper installation or application The warranty does not extend to products that have been repaired or altered outside our factory without our written approval Except as provided above Keltron Corpo...

Page 48: ...42...

Page 49: ...only and do not network more than 15 panels Otherwise ambiguous SIA Zone numbers will result Also please verify that the central station receiver and central station automation computer are compatibl...

Page 50: ...FV Fire Supervision Restoral MLT EVENTS UA Untyped Zone Alarm UH Untyped Alarm Restore SHORT DISCONNECT MISSING WRONG TYPE EXTRA ADDR CONFIG ERR LOOP BREAK FT Fire Trouble FR Fire Restoral TEST FAIL...

Page 51: ...added to the field programmed account numbers For example if the programmed account number is 1000 then events from unit number 1 ALU1 QZU1 EZU1 report on account 1000 Events from unit number 2 will...

Page 52: ...ORMAL FS Fire Supervisory FV Fire Supervision Restoral SHORT CM SHORT DISCONNECT MISSING WRONG TYPE EXTRA ADDR CONFIG ERR TROUBLE LOOP BREAK FT Fire Trouble FR Fire Restoral TEST FAIL DIRTY VERY DIRTY...

Page 53: ...No conversion is necessary for the detectors modules and notification appliance circuit point IDs Those point IDs are transmitted directly as the 4 digit SIA zone number The EST2 panel fault point ID...

Page 54: ...RVISORY FS Fire Supervisory FV Fire Supervision Restore SHORT FAULT OPEN FAULT FT Fire Trouble FR Fire Restoral OPEN FAULT Battery YT System Battery Trouble YR System Battery Restoral OPEN FAULT Prima...

Page 55: ...is necessary for the detectors modules and notification appliance circuit point IDs Those point IDs are transmitted directly as the 4 digit SIA zone number The MIR2 panel fault point IDs are converted...

Page 56: ...RVISORY FS Fire Supervisory FV Fire Supervision Restore SHORT FAULT OPEN FAULT FT Fire Trouble FR Fire Restoral OPEN FAULT Battery YT System Battery Trouble YR System Battery Restoral OPEN FAULT Prima...

Page 57: ...CW Was Force Armed CX Custom Function Executed CZ Point Closing DA Card Assigned DB Card Deleted DC Access Closed DD Access Denied DE Request to Enter DF Door Forced DG Access Granted DH Door Left Op...

Page 58: ...ld JO Log Overflow JP User On Premises JR Schedule Executed JS Schedule Changed JT Time Changed JV User Code Changed JX User Code Deleted JY User Code Added JZ User Level Set KA Heat Alarm KB Heat Byp...

Page 59: ...Alarm SB Sprinkler Bypass SC Change of State SH Sprinkler Alarm Restore SJ Sprinkler Trouble Restore SR Sprinkler Restoral SS Sprinkler Supervisory ST Sprinkler Trouble SU Sprinkler Unbypass TA Tamper...

Page 60: ...Trouble YE Receiver Line Card Restored YF Parameter Checksum Fail YG Parameter Changed YH Bell Restored YI Overcurrent Trouble YJ Overcurrent Restore YK Communications Restoral YM System Battery Missi...