13
Restore to Normal Operation
Zone Restores
For a status change to a restore condition on a given alarm zone input:
If restoring from alarm:
The alarm LED for that alarm zone input goes out.
If no other monitored conditions require the common alarm relay to be active, it returns to its
normal state
,
and the alarm contact active LED goes out.
If no other monitored conditions require the audible to be active, the audible is silenced.
The programmed (or default) alarm restore event code is transferred to the SIA transmitter. (see
dialing operation)
If restoring from trouble:
The trouble LED for that alarm zone input goes out.
If no other monitored conditions require the common trouble relay to be active, it returns to its
normal state, and the trouble contact active LED goes out.
If no other monitored conditions require the audible to be active, the audible is silenced.
The programmed (or default) trouble restore event code is transferred to the SIA Transmitter. (see
dialing operation)
For a status change to the normal condition on the AC failure (zone 5), low battery (zone 6), or
no/missing battery (zone 7) power monitor zone inputs:
If all of the power monitor zones are normal, the power fault LED goes out.
If no other monitored conditions require the common trouble relay to be active, it returns to its
normal state, and the trouble contact active LED goes out.
If no other monitored conditions require the audible to be active, the audible is silenced.
The programmed (or default) power monitor restore event code is transferred to the SIA
transmitter. (see dialing operation)
Note that the normal condition (normally open or normally closed) for zones 5, 6, and 7 is determined by
user jumpers 5, 6, and 7 respectively.
Serial Port Restore (SDACT only)
(For supplementary use only) If a serial port trouble condition was previously detected, and either the
condition restores to normal or user jumper J4 is removed to disable serial port supervision:
The serial trouble LED goes out.
If no other monitored conditions require the common trouble relay to be active, it returns to its
normal state, and the trouble contact active LED goes out.
If no other monitored conditions require the audible to be active, the audible is silenced.
The ER (expansion restore) event code is transferred to the SIA transmitter. (see dialing operation)