Installation
C2N Series Tankless Heater
Bradley •
215-1821 Rev. B; ECN 16-17-005
5/3/2016
Output heating capacity is reduced if these heaters are installed on 415V, 400V or 380V 3-ph .
Contact the factory to supply this information .
Satisfactory performance of the heater is dependent upon a specific flow rate vs temperature rise capability . If the
desired temperature is not achieved, please verify the following:
1 . Circuit breaker is on and rated for the maximum power draw .
2 . Heater is drawing the proper current for the supply voltage on all 3 phases .
3 . All 3 phase indicator lights are lit (not flashing) indicating maximum power draw and maximum
amperage is being drawn .
4 . Flow rate and temperature rise in the water heating process are compatible with the heater specifications .
5 . Verify there is no additional supply of cold water entering the line downstream of the heater .
Product Options
GF (Ground Fault):
Detects electrical leakage from external sources to protect equipment, electronics, and the heat
exchanger from being damaged in the event of a power fault . After turning on water, then power, test ground fault:
1 . Press GF Test button .
2 . Watch for ground fault light to illuminate and Bank Ready light(s) to shut off . The Ground Fault system is active
and in working order .
3 . Press the GF Reset button, hold for 2 seconds and release to reset ground fault .
FDS Fused Disconnect:
Internal fused disconnect interlocks with enclosure door when energized, prohibiting access
to a live cabinet . Select the FDS option for an additional level of safety and convenience at the heater location .
T190 High Temperature Option:
Reach and maintain temperatures as high as 190°F (88°C) .
D1 Control Interface:
Provides 4–20ma communication interface with temperature controller .
TE & TE2 Corrosive Fluid Protection:
The TE option is a PFA Teflon
®
coated heat exchanger with bright annealed
stainless steel elements,FDA Approved (use for deionized water or mild corrosive fluid applications) . Similar to TE,
the TE2 option is a single layer of Xylan Fluoropolymeric coated heat exchanger with bright annealed stainless steel
elements, FDA Approved for Food Contact (use in deionized water applications) .
EXP2 (Explosion Proof Purge System):
Keltech's EXP2 option makes heaters compliant for classified areas;
Class I Division 2, Groups A, B, C, D, Temp Code: T5 . The Purge System requires a supply of clean instrument air or
inert gas (provided by installer) . This supply maintains a positive internal pressure and prevents the enclosure from
filling with flammable gases, dusts or vapors from the ambient environment . Complete installation provided in this
manual .
Low Flow (L5):
0 .50 GPM (1 .9 lpm) option for heating water when lower flow rates are required .
N4X (NEMA 4X Enclosure):
Corrosion resistant enclosure made of stainless steel and ideal for harsh environments .
If a trip occurs under normal operation DO NOT RESET Ground Fault without evaluation and
service.
Normal state is Ground Fault light OFF, Bank Ready lights ON.