Kelly KLS-8080N/NPS Sinusoidal BLDC/PMSM Controller User
’s Manual
V1.13
33
Usually we just need to configure two parameters in user program according to the specification
of Sin/Cosin speed sensor. Please click Motor button in the user program.
Line hall zero: The line hall zero point is at 3Vdd/5=3*5V/5=3.0V.So we need to fill
3*1023/5=613.8=614 for Line hall zero parameter instead of 508 in the user program.
Line hall amplitude: The document showed the Amplitude is 1.1V
±
0.2V.We think the amplitude
is 1.1V for now. So we need to fill 1.1*1023/5=225 for line hall amplitude instead of 410 in the
user program.