Kelly KLS-8080N/NPS Sinusoidal BLDC/PMSM Controller User
’s Manual
V1.13
37
Caution:
•
Make certain that the motor is connected before trying to run Identification angle
function in the configuration software.
The controller needs to be connected to
batteries, motor and throttle before Identification operation. That is to say, it is
not enough to connect only power supply(PWR=pin7) to batteries for
Identification Angle operation.
•
Configuration software will be regularly updated and published on the website. Please
Update your Configuration Software regularly. You must uninstall the older version
before updating.
•
Please try to use Identify function for motor and hall sensors in the user program
Table 1: ERROR CODES
Buzzer Error Codes
Code
Explanation
Solution
1,1
¤ ¤
Automatic error
identification
1. Wrong wiring of motor phase line or hall.
Please suspend the motor when enable
Auto-Identify function.
1,2
¤ ¤¤
Over voltage error
2. Battery voltage is too high for the controller.
Check battery volts and configuration.
3. Regeneration over-voltage. Controller will have
cut back or stopped regen.
4. This only accurate to
±
2% upon Overvoltage
setting.
1,3
¤ ¤¤¤
Low voltage error
1. The controller will clear after 5 seconds if battery
volts returns to normal.
2. Check battery volts & recharge if required.
1,4
¤ ¤¤¤¤
Reserved
2,1
¤¤ ¤
Motor did not start
Motor did not reach 25 electrical RPM within 2
seconds of start-up. Hall sensor or phase wiring
problem.
2,2
¤¤ ¤¤
Internal volts fault
1. Measure that B+ & PWR are correct when
measured to B- or RTN.
2. There may be excessive load on the +5V supply