CT Primary
Switch C1
Switch C2
Switch C3
Switch C4
Switch C5
5
Off
Off
Off
Off
Off
50
Off
Off
Off
Off
On
75
Off
Off
Off
On
Off
100
Off
Off
Off
On
On
150
Off
Off
On
Off
Off
200
Off
Off
On
Off
On
250
Off
Off
On
On
Off
300
Off
Off
On
On
On
400
Off
On
Off
Off
Off
500
Off
On
Off
Off
On
600
Off
On
Off
On
Off
750
Off
On
Off
On
On
800
Off
On
On
Off
Off
1000
Off
On
On
Off
On
1200
Off
On
On
On
Off
1500
Off
On
On
On
On
1600
On
Off
Off
Off
Off
2000
On
Off
Off
Off
On
2500
On
Off
Off
On
Off
3000
On
Off
Off
On
On
3500
On
Off
On
Off
Off
4000
On
Off
On
Off
On
5000
On
Off
On
On
Off
6000
On
Off
On
On
On
mA Output #2
mA Output #1
Signal Selected for mA Output
Switch
Switch
Switch
Switch
Switch
Switch
B3
B4
B5
B6
B7
B8
Total KW
Off
Off
Off
Off
Off
Off
15- minute Sliding Window KW
Off
Off
On
Off
Off
On
Peak Sliding Window KW
Off
On
Off
Off
On
Off
Total KVA
Off
On
On
Off
On
On
Total Power Factor
On
Off
Off
On
Off
Off
RMS Current
On
Off
On
On
Off
On
RMS Voltage
On
On
Off
On
On
Off
KWH Per Pulse
Switch B1
Switch B2
0.01
Off
Off
0.1
Off
On
1
On
Off
10
On
On
TABLE 4 mA OUTPUT SIGNAL SELECTIONS
TABLE 5 CT RATIO SELECTIONS (5 Amp or 1 Amp or 0.333 Volt CT’s)
Low Volts Threshold
Switch A3
Switch A4
Switch A5
Switch A6
Switch A7
Switch A8
294
On
Off
On
On
Off
On
304
On
Off
On
On
On
Off
312
On
Off
On
On
On
On
321
On
On
Off
Off
Off
Off
332
On
On
Off
Off
Off
On
341
On
On
Off
Off
On
Off
353
On
On
Off
Off
On
On
360
On
On
Off
On
Off
Off
374
On
On
Off
On
Off
On
384
On
On
Off
On
On
Off
396
On
On
Off
On
On
On
408
On
On
On
Off
Off
Off
432
On
On
On
Off
Off
On
480
On
On
On
Off
On
Off
510
On
On
On
Off
On
On
540
On
On
On
On
Off
Off
TABLE 3 KWH PER PULSE
Table 2 - continued