background image

KELE • www.kele.com • FAX 901-372-2531

USA 901-937-4900 • International 901-382-6084

4

DIP SWITCHES
Setting the DIP switches according to system requirements is suggested before applying power to the PowerTrak. However, it is
not necessary to remove power from the PowerTrak in order to make  changes to the DIP switch settings.
A1 - A2: Define the power system type. Set these switches to match the type of system that is to be monitored. Select from 

3-Phase wye or delta and single-phase 2-wire or 3-wire systems. See Table 1 for switch settings.

A3 - A8: Define the low voltage alarm threshold. Select an appropriate value for the system voltage that is monitored. 

For delta systems, low voltage is measured line-to-line. For wye and single-phase systems, low voltage is measured 
line-to-neutral. Select from alarm threshold values ranging from 51 to 540 volts. See Table 2 for switch settings

B1 - B2: Define the KWH per pulse value. Set these switches to obtain an optimum pulse rate that can be read by the BAS 

controller or data acquisition equipment. Select from 10, 1, 0.1, and 0.01 KWH per pulse values.  See Table 3 for 
switch settings.

B3 - B5: Define mA loop #2 signal type. Set these switches for the power parameter to be represented by this 

4-20 mA output. Select from seven different parameters, Total KW, Window KW, Peak Window KW, Total KVA, 
Total Power Factor, True RMS Voltage*, True RMS Current*. 
See Table 4 for switch settings.

B6 - B8: Define mA loop #1 signal type. Set these switches for the power parameter to be represented by this 

4-20 mA output. Select from seven different parameters, Total KW, Window KW, Peak Window KW, Total KVA, 
Total Power Factor, True RMS Voltage*, True RMS Current*.  
See Table 4 for switch settings.

C1 - C5: Define the current transformer ratio. Set switches to match the primary current rating of the current transformers con-

nected to the PowerTrak. Select from CT primaries ranging from 50 to 6000. See Table 5 for switch settings.

* Voltage and current outputs are the average of the three-phase true RMS values.
SYSTEM VOLTAGE SELECT SWITCH
Set the SYSTEM VOLTAGE SELECT switch to the correct line-to-line system voltage (or potential transformer secondary volt-
age, if used) connected to the PowerTrak. If the actual system voltage is greater than the selector switch setting, the over volt-
age LED will flash and the PowerTrak will cycle on and off to protect itself from over voltage. If this occurs, turn the selector
switch to the correct system voltage setting.

AUTO-CONFIGURATION
After all wiring connections are completed, the DIP switches are set correctly,  the voltage selector switch is set to the correct sys-
tem voltage, and the electrical system is energized,  the PowerTrak can be auto-configured. To initiate the auto-configuring system,
press the AUTO-CONFIG button. The PowerTrak will examine the current and voltage waveforms for correct phasing and CT polar-
ity. During the auto-configuring process, the Volts/Amps phasing LED’s and CT reverse polarity LED’s will light in sequence. When
the process is completed only one of the Volts/Amps phasing LED’s will be lighted indicating the actual phasing between the voltage
and current inputs to the PowerTrak. A lighted CT polarity LED indicates that the corresponding CT is installed or wired backwards
giving a reverse polarity. A correctly wired PowerTrak will be indicated by all CT polarity LED’s extinguished and the left most
Volts/Amps phasing LED lighted. Should any of the other phasing or CT polarity LED’s be lighted, the PowerTrak will electronically
“fix” the wiring errors and provide correct and accurate outputs. No time consuming troubleshooting or wire swapping is required.
Note: The Auto-Configuration and Manual Configuration functions cannot be used with summing current tranformers. Proper wiring
of CT’s and voltages must be observed when using summing CT’s.
If the auto-configuring system is unable to determine the correct wiring configuration, the PowerTrak will enter the manual con-
figuration mode and the manual config yellow LED will light. If this occurs, try initiating the auto-configuring system again, by
pressing the Auto-config button. If the manual config yellow LED lights again then check the following:
1. Verify all switch settings on the PowerTrak are correct for the monitored electrical system.
2. Verify all phase voltages are present at the SYSTEM VOLTAGE terminal block using a voltmeter and/or the PowerTrak dis-
play option.
3. Verify all Current Transformer inputs are present at the CT INPUTS terminal block using a clamp on ammeter and/or the
PowerTrak display option. Current transfomer secondary wires (X1 & X2) should be connected to the PowerTrak in pairs.
NOTE:  For the auto-configuring system to function properly, these four conditions should be met:
1. Load amperage must be above 5% of the CT primary rating.
2. The system power factor must be greater than 0.64 lagging.
3. The power factor should not be leading.
4. The power system waveform does not have severe harmonic distortion.
After checking these items and making any corrections, press the AUTO-CONFIG button again. If the PowerTrak is still unable
to determine the correct wiring configuration, Manual Configuration will be required.

MANUAL CONFIGURATION
The electrical system load should be relatively constant during the manual configuration procedure. To manually configure the
PowerTrak, set the DIP switches so that one of the 4-20 mA outputs represents Total KW. Connect a meter set to read DC milliamps to
this output, or if the PowerTrak has the LCD display option, set one of the display lines to read Total KW. Next, press the manual config
CT polarity button (CT POL) to scan through the different CT polarity combinations. Each time record the reading of theTotal KW display
or mA output. Allow the reading to stabilize before recording it.  After reviewing all of the CT polarity combinations, press the manual con-
fig V-A MATCH button and repeat the process of scanning through the CT polarity combinations. After trying all possible combinations of
V-A match and CT polarity (there are 48 possible combinations, see the manual configuration worksheet) the correct configuration is the
one producing the highest value of KW on the display or the highest mA reading on the meter. Manually set the PowerTrak to the cor-
rect configuration using the CT POL & VA MATCH push buttons.

POWERTRAK CONFIGURATION

Summary of Contents for PowerTrak Series

Page 1: ...ptional LonWorks communications APPLICATION PowerTrak Applications Remote Outputs Local Display Monitoring KWH Total KW Window KW Peak Window KW Total KVA Total Power Factor PF True RMS Voltage True RMS Current Local Display Monitoring Each Phase True RMS Voltage True RMS Current KW Wye systems KVA Wye systems Power Factor Wye systems Inputs System type Three phase Wye or Delta Single Phase Input ...

Page 2: ... read by the PowerTrak The jumper plugs should be placed in the SHORT position before the shorting assembly is disconnected from the PowerTrak Current Transformer CT Installation Note When using current transformers with small burden load capability typically CT s with ratios below 200 5 the CT secondary wiring can add significantly to the burden that must be supported by the CT For these applica ...

Page 3: ...d with the communications module for information on wiring protocols etc INSTALLATION Continued The PT 9000 may be ordered with an optional two line 16 character alpha numeric LCD display for local monitor ing of power parameters Each line of the display can be manually scrolled with the yellow cover mounted buttons to view up to 23 different displayed parameters No calibration of the display is r...

Page 4: ... indicating the actual phasing between the voltage and current inputs to the PowerTrak A lighted CT polarity LED indicates that the corresponding CT is installed or wired backwards giving a reverse polarity A correctly wired PowerTrak will be indicated by all CT polarity LED s extinguished and the left most Volts Amps phasing LED lighted Should any of the other phasing or CT polarity LED s be ligh...

Page 5: ...Off Off 102 Off Off On On Off On 104 Off Off On On On Off 106 Off Off On On On On 108 Off On Off Off Off Off 111 Off On Off Off Off On 113 Off On Off Off On Off 114 Off On Off Off On On 116 Off On Off On Off Off 118 Off On Off On Off On 123 Off On Off On On Off 125 Off On Off On On On 130 Off On On Off Off Off 160 Off On On Off Off On 170 Off On On Off On Off 176 Off On On Off On On 180 Off On On ...

Page 6: ...itch B3 B4 B5 B6 B7 B8 Total KW Off Off Off Off Off Off 15 minute Sliding Window KW Off Off On Off Off On Peak Sliding Window KW Off On Off Off On Off Total KVA Off On On Off On On Total Power Factor On Off Off On Off Off RMS Current On Off On On Off On RMS Voltage On On Off On On Off KWH Per Pulse Switch B1 Switch B2 0 01 Off Off 0 1 Off On 1 On Off 10 On On TABLE 4 mA OUTPUT SIGNAL SELECTIONS TA...

Page 7: ...0 mA OUTPUT 1 OVER VOLTS LED X2 X1 X2 X1 X2 X1 A NORM SHORT B NORM SHORT C NORM SHORT OPTIONAL CT SHORTING ASSEMBLY DETAIL SYSTEM VOLTAGE SELECT SWITCH 600 V 120 144 V 190 277 V MAKE CT CONNECTIONS TO THESE TERMINALS CTC CTB CTA CT shorting jumpers shown in the normal position CT shorting assembly pins secured to PT 9000 CT Inputs Terminal Block PT 9000 SERIES OPTIONAL COVER MOUNTED LCD DISPLAY DE...

Page 8: ...s updated on thirty second intervals and will change in value only if the current sliding window KW value is greater than the current peak window KW value KELE www kele com FAX 901 372 2531 USA 901 937 4900 International 901 382 6084 8 X2 X1 H1 CT L N L N L I N E L O A D CT H1 should face Line side CTC X2 X1 CTB X2 X1 CTA X2 X1 CT INPUTS SYSTEM VOLTAGE CONNECTIONS NEUTRAL L3 L2 L1 No Connection No...

Page 9: ...VA The Total KVA parameter is the total instantaneous KVA demand for a three phase or single phase electrical system Three phase equation Single phase equation KVA E x I x 1 73 x mA out 4 KVA E x I x mA out 4 1000 x 16 1000 x 16 Where KVA Total KVA value E 144 SYSTEM VOLTAGE SELECT switch set to 120 144 V 277 SYSTEM VOLTAGE SELECT switch set to 190 277 V 415 SYSTEM VOLTAGE SELECT switch set to 346...

Page 10: ...of the CT ratio selected with DIP switch C1 C5 ex CT ratio 500 for 500 5 ratio mA out PowerTrak milliamp output value for True RMS Current DIGITAL OUTPUTS KWH Pulse Output The PowerTrak provides a contact closure pulse output representing energy consumption KWH By setting the appropriate DIP switches B1 B2 See Table 3 each pulse will represent either 10 1 0 1 or 0 01 KWH per pulse The 10 KWH per p...

Page 11: ...IP switch C1 C5 ex I 500 for 500 5 ratio KWH pulse KWH per pulse setting from DIP switches B1 B2 See Table 3 PT Ratio PT Primary PT Secondary Example 4800V to 120V PT Ratio 4800 120 40 Low Voltage Alarm Contact SYS VOLTS OK The Low Voltage Alarm Contact is a normally open contact that closes when any phase voltage drops below the low voltage alarm setting determined by DIP switches A3 A8 See Table...

Page 12: ...on is installed on the PowerTrak place the shorting jumpers in the NORM position ____5 Set the SYSTEM VOLTAGE SELECT switch to the line to line voltage of the electrical system to be monitored ____6 Set the Power System Type DIP switches A1 A2 ____7 Set the Low Voltage Alarm Threshold DIP switches A3 A8 ____8 Set the KWH Pulse rate if used DIP switches B1 B2 ____9 Set the mA output 2 for the desir...

Reviews: