KELE • www.kele.com • FAX 901-372-2531
USA 901-937-4900 • International 901-382-6084
12
ORDERING INFORMATION
PT-9500
PowerTrak Power Monitoring Interface, 5 Amp CT Input
PT-9300
PowerTrak Power Monitoring Interface, 0.333 Volt CT Input
PT-9100
PowerTrak Power Monitoring Interface, 1 Amp CT Input
Options
D
LCD Display, Cover Mounted For Local Monitoring
S
CT Shorting Assembly (Not Necessary For PT-9300)
3R
PowerTrak Mounted In A NEMA 3R Enclosure
Example: PT-9500-D-S PowerTrak with LCD display and
CT shorting assembly
PT-9500
D
S
Related Products
PT-NTL-10
LonWorks Commuications Module
AL12AR
Cylinder Lock Kit
U3889-E
Shorting/disconnect assembly
____ 1. Mount the PowerTrak using the proper hardware for the type of wall construction involved. Pull the conduit
and wiring to any of the eight 1/2" knockouts.
____ 2. With the electrical system de-energized, make all CT and voltage connections per instructions.
____3. Make wiring connections to the output signal terminals for the KWH pulse, low-voltage alarm contact, and both
4-20 mA signals (if used).
____4. If the shorting assembly option is installed on the PowerTrak, place the shorting jumpers in the NORM
position.
____5. Set the SYSTEM VOLTAGE SELECT switch to the line-to-line voltage of the electrical system to be monitored.
____6. Set the Power System Type, DIP switches A1-A2.
____7. Set the Low Voltage Alarm Threshold, DIP switches A3-A8.
____8. Set the KWH/Pulse rate (if used), DIP switches B1-B2
____9. Set the mA output #2 for the desired parameter (if used), DIP switches B3-B5.
___10. Set the mA output #1 for the desired parameter (if used), DIP switches B6-B8.
___11. Set the CT ratio for the current transformer primary rating used. DIP switches C1-C5.
___12. With the electrical system energized and under load, press the AUTO-CONFIG button to auto-configure the
PowerTrak. After scanning the electrical connections the auto-config LED's will display the actual electrical
connections to the PowerTrak, electronically ”correct“ wiring errors, and provide accurate output signals. If the
MANUAL CONFIG LED lights, follow instructions in this data sheet.
___13. If equipped with the display option, verify that all parameters display a value.
___14. Verify that all output signals used are working properly.