3 Installation
Hybrid Inverter
User Manual
32
Figure3-29 External grounding connection
The grounding of the inverter and the lightning rod of the building that inverter installed cannot
be the same, the two need to be separated (as shown in Figure3-30), or, lightning stroke will
damage the inverter.
The grounding of the inverter should be directly connected to the grounding system, and the
impedance should be less than 20m
Ω
.
Figure3-30 Grounding diagram of inverter
----End
3.5.3 DC Input (PV) Connection
When installation, it must use the equipped DC terminals to avoid inverter damage.