6 Routine Maintenance
All rights reserved © Kehua Data Co., Ltd.
65
6 Routine Maintenance
This chapter mainly introduces the maintenance and safety precautions, preventive maintenance and
maintenance procedure, etc.
6.1 Maintenance Guide
The correct maintenance is the key of the best operation for PCS. It can prolong the device service
life.
6.1.1 Machine Room Management
Room management include room environment security management and device management .The
job of room environment security management is to keep the room temperature, humidity, cleanliness,
static, noise, EMI meet the requirement ,and to ensure power supply properly. The requirement of
device management is to keep mechanical properties intact, electric properties meet a criterion,
device operation steady and data complete. The maintenance checking items are showed inTable6-1
(only for reference).
Table6-1
Checking items
NO.
Checking items
Cycle
1
Temperature and humidity
Daily
2
Cleanliness of control room and other rooms
Daily
3
Cleanliness of cabinet and platform surface
weekly
4
Performance of temperature and humidity alarm
weekly
5
Air condition filter clean and replacement
Monthly
6
Resistance measuringof anti-static staging, ground, seat and wrist strap.
Monthly
7
SPD (before thunderstorm season)
Season
8
Fixed gas extinguishing device
Yearly