P30
Readable Data
Modbus TCP Programmers Guide V1.02
10
© KEBA
3.3
1006 - Error code
This register contains the error code of the charging station.
Index
Name
Type
Attr.
1006
EVSE Error Code
UINT32
ro
Supported values:
●
0: No error
●
>1: Specific error code. The represented value is in decimal and has to
be converted to hex in order to read the error code. E.g. 262144 con-
verted to hex = 40000, that stands for error group 4.
3.4
1008 - Charging current phase 1
This register contains the measured current value on phase 1 in mil-
liamperes.
Unit: mA
Index
Name
Type
Attr.
1008
Current L1
UINT32
ro
Example:
Value 645: The charging current on phase 1 is 645 mA = 0.645 A.
3.5
1010 - Charging current phase 2
This register contains the measured current value on phase 2 in mil-
liamperes.
Unit: mA
Index
Name
Type
Attr.
1010
Current L2
UINT32
ro
Example:
Value 1011: The charging current on phase 2 is 1011 mA = 1.011 A
3.6
1012 - Charging current phase 3
This register contains the measured current value on phase 3 in mil-
liamperes.
Unit: mA
Index
Name
Type
Attr.
1012
Current L3
UINT32
ro