E10
Operating behavior
V1.00
20
© KEBA 2023
8
Operating behavior
8.1
Restarting the device
To restart the device, the reset button must be pressed with a pointed object
for at least 6 seconds. Then the device restarts. The measured values are
not available for approx. 5 sec. after a restart.
A restart of the device can also be triggered using the Modbus TCP protocol.
To do so, the value 1 must be written to Modbus register 61615 (
0xF0AF
).
8.2
Resetting the device to factory settings
To reset the device to factory settings, proceed as follows:
1) Press the reset button with a pointed object briefly 1x (approx. 0.5 sec-
onds)
2) Then press and hold 1x (3 to 5 seconds) within 1 second.
If the input is successful, the status LED flashes orange twice and the device
has been reset to the factory setting. If the input fails, you must wait 2 sec-
onds before a new input attempt can be performed.
8.3
Behavior in the event of voltage drop
As soon as a lower power supply is detected, the device saves the mea-
sured energy values in non-volatile memory.