3.3.1 Incremental TTL
Encoder Interface X3A
Screw Terminals
Connect the incremental encoder mounted on the motor to the 8-posi-
tion terminal connector at X3A. This connection provides speed feed-
back and is imperative to the proper operation of the F5.
ONLY when the inverter is switched off and the volt-
age supply is disconnected may the feedback con-
nectors be removed or connected!
X3A
Channel 1
X3B
Channel 2
X3A
Channel 1
X3B
Channel 2
Plug in screw
terminal X3A
Pin No.
Signal
Description
1
A+
TTL incremental encoder track A
2
A-
Differential signal to A+
3
B+
TTL incremental encoder track B
4
B-
Differential signal to B+
5*
N+
TTL Zero track
6*
N-
Differential signal to N+
7**
15/24 V
Voltage output 15/20...30 V, power supply for
the encoder, switchable with dip switch S100
8
COM
0V reference for voltage supply
-
GND
Connect the outer cable shield to an earth
ground connection on the elevator drive
*If the encoder has no zero channel, connect N+ (X3A.5) to 5V (X3B.7) and
N- (X3A.6) to 0V common (X3A.8 or X3B.8) to avoid ‘Error Encoder1’ faults.
**For 5V supply TTL encoders, a 5V supply is available on the second inter-
face channel, X3B.7.
i
TTL Incremental Terminal Strip - Encoder Connections
53