background image

9

every calibration. Position near primary thermostat
(center) bulb is recommended.

4.

Pre-2000 model: If calibration of thermostat is found
to be less than 15°F(9.44°C) off, simply loosen
three dial plate retaining screws, rotate dial plate to
match thermometer reading and tighten screws. 

2000-model: If calibration is found to be less than
15°F (9.44°C) off, remove thermostat knob. Loosen
four screws in thermostat dial plate. Replace knob.
Reset dial plate to match thermometer reading.
Remove knob to tighten screws on dial plate and
replace knob.

If the thermostat is more than 15°F(9.44°C) off then
a qualified service company must be contacted to
have the Pasta System properly calibrated.

Figure 4-2

Thermostat calibration (pre-2000 model shown)

Thermostat Calibration 2000 Model

(Thermostat knob removed to

reveal calibration screws.)

B. The Water Auto-Fill and Low Water Safety Shut-

Off Systems

The water supply connection, located at the bottom rear
of the Pasta System and marked water, is a standard 

3

/

8

female pipe connection. The water pressure should be
between 20-60 psi. If the pressure exceeds 60 psi, a
pressure regulator must be used. The water
temperature must not exceed 150°F(65.6°C). Hot or
warm water is not needed due to the instant recovery of
the Pasta System.

Connections suitable for hot water must be used.
All connections must be tested for leaks before
using the Pasta System.

NOTE: 

For Pasta Systems with casters, flexible hose

must be used to avoid leaking when the Pasta System
is moved for cleaning.

Control of the water level is fully automatic with the
auto-fill system. The water level is controlled by two
circuit boards and two sensors. The sensors are located
in the tube on the right side of the overflow deck. The
upper sensor controls the water level and the lower
sensor controls the low water safety shut-off system.
Once the water On/Off switch is turned on, the blue light
will come on and start to fill until the water level reaches
the upper sensor. The burners will not come on until the
water level reaches the lower sensor, preventing the
Pasta System from being damaged if there is little or no
water in it. Both sensors must be cleaned with the
sensor brush (like the one provided) on an hourly basis
or whenever starch foams up to maintain the proper
water level. Sensors must be cleaned more often in
areas with hard water, in installations with softened
water (due to the salt in the water) or when oil or salt is
placed in the water for cooking.

The brush must be checked on a regular basis and
replaced whenever it starts to wear.

Do not store the sensor brush in the sensor tube as
it could contact the sensors, which could allow the
water level to drop below the heat tubes and
damage the Pasta System.

Using a worn brush could damage the sensors.

NOTE: 

Water level problems caused by the sensors

not being cleaned adequately will not be covered under
warranty.

WHEN THE WATER LEVEL FALLS BELOW THE
LOWER SENSOR THE BURNERS WILL SHUT OFF.
IF THEY STAY ON, TURN THE MAIN POWER
ON/OFF SWITCH TO THE “OFF” POSITION AND
CLEAN THE SENSORS THOROUGHLY. IF THE
PROBLEM STILL OCCURS, HAVE THE WATER
AUTO-FILL SYSTEM CHECKED BY A QUALIFIED
SERVICE TECHNICIAN.

Figure 4-3 Sensor Tube Location

Summary of Contents for INSTANT RECOVERY SERIES 2009

Page 1: ...CTION VII WIRING DIAGRAMS 14 ELECTRIC PASTA WITHOUT TIMERS 15 14 ELECTRIC PASTA WITH DIGITAL TIMERS 16 14 ELECTRIC PASTA WITH 138 BLACK DIAL TIMERS 17 14 ELECTRIC PASTA WITH BASKET LIFT DIGITAL TIMERS...

Page 2: ...er of all warrant and liability Keating of Chicago Inc manufacturer reserves the right to change specifications at any time IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE...

Page 3: ...ic timers Low water safety shutoff 1 full port front drain valve on 14 11 4 for 18 and larger High temperature limit control with manual reset Patented accurate temperature control system 2 F Ideal 35...

Page 4: ...anel before servicing NEVER leave a pasta system unattended during operation NEVER move a pasta system when full of hot water NEVER introduce objects or liquids into pasta system while operational whi...

Page 5: ...a claim with the carrier since such damage is the carrier s responsibility By following these instructions carefully we guarantee our full support of your claims to protect you against loss from conce...

Page 6: ...device or its associated piping to limit the appliance movement Connectors must comply with ANSI Z21 69 CAN1 CAN CGA 6 16 latest edition for connectors for movable gas appliances Quick disconnect dev...

Page 7: ...difference between the two thermostats Having less than a twenty degree difference will increase the possibility of a boil over and cause the pasta cooker to short cycle The recommended starting tempe...

Page 8: ...t Lift Model 1 Fill Pasta System as described on page 6 Filling 2 Set primary left thermostat to 212 F 100 C and secondary right thermostat to 190 F 87 8 C 3 Fill basket s to proper level and place on...

Page 9: ...turn ON and the display will now be indicating OR The BEEPER will BEEP 4 times NOTE If STEP 1 was OK proceed to STEP 2 If not retry Step 1 making sure the power was OFF for at least 30 seconds or more...

Page 10: ...any maintenance problem is directly or indirectly related to cleanliness NOTE Water level problems caused by the sensors not being cleaned adequately will not be covered under warranty NOTE Use of sod...

Page 11: ...cleaning Control of the water level is fully automatic with the auto fill system The water level is controlled by two circuit boards and two sensors The sensors are located in the tube on the right si...

Page 12: ...it The potentionmeter adjusts the sensitivity of the probe Adjusting this sensor will not increase the depth of the water Improper adjustments can effect the operation of the cooker and cause damage...

Page 13: ...not minutes or seconds 1 Reset the timer see pages 8 9 Water leaking in the rear of the pasta cooker 1 Replace fill hose Part 037390 sold per foot Breakers continue to trip 1 Ensure all wires to the c...

Page 14: ...echanism does not operate a Connections are loose or timer is faulty b Motor limit switch is faulty c Lift motor is faulty d Actuator is faulty e Control circuit fuse has blown f Relay is faulty a Tig...

Page 15: ...Fig 7 1 Custom Pasta System Electric Control Panel 1 2 3 2 4 5 6 6 7 7 ORDERING PARTS Parts may be ordered by part number by calling Keating at 1 800 KEATING or your local servce company You may also...

Page 16: ...SMALL 002565 CIRCUIT BREAKER 40AMP 1P 012129 4 6 6 4 FUSE 300V 3AMP 004334 2 2 2 2 CONTACTOR 110V 3P 50AMP 011225 3 3 3 2 CONTRACTOR 110V 4P 40AMP 005597 1 TRANSFORMER STEPDOWN 004376 1 1 1 1 220 110V...

Page 17: ...15 VII WIRING DIAGRAMS 14 ELECTRIC PASTA 2 THERMOSTAT WIRING DIAGRAM WITHOUT TIMERS 2...

Page 18: ...14 ELECTRIC PASTA WITH DIGITAL TIMERS WIRING DIAGRAM 16...

Page 19: ...17 14 ELECTRIC PASTA WITH 138 TIMERS WIRING DIAGRAM PRE 2000 SERIES BLACK DIAL TIMER NOT DIGITAL...

Page 20: ...18 14 ELECTRIC PASTA WITH BASKET LIFT AND DIGITAL TIMERS WIRING DIAGRAM...

Page 21: ...19 18 20 ELECTRIC PASTA WITH 138 TIMERS WIRING DIAGRAM PRE 2000 SERIES BLACK DIAL TIMER NOT DIGITAL...

Page 22: ...20 18 ELECTRIC PASTA 2 THERMOSTAT WIRING DIAGRAM WITHOUT TIMERS...

Page 23: ...21 24 ELECTRIC PASTA WITH DIGITAL TIMERS WIRING DIAGRAM...

Page 24: ......

Page 25: ...______________ INVOICE NUMBER __________________________ SERIAL NUMBER ______________________________ FRYER FILTER SYSTEM GRIDDLE REMARKS ____________________________________ TOP SIDE COOKER HOT PLATE...

Reviews: