KE 4256-3230 Keatec T Series UPS 10-40K 380Vac Users Guide English 20170126 This manual is for qualified personnel only.
Page 10
10-20kVA:
Terminal sequence from left to right: Input phase A(L1), input phase B(L2), input phase C(L3), input
Neutral line, output phase A(L1), output phase B(L2), output phase C(L3), output Neutral line, battery
positive, battery Neutral, battery negative. There are 3 connectors for GROUND under the terminal
block.
30-40kVA:
Terminal sequence from left to right: Input phase A(L1), input phase B(L2), input phase C(L3), input
Neutral line, output phase A(L1), output phase B(L2), output phase C(L3), output and battery Neutral
line, battery positive, battery negative. There are 3 connectors for GROUND under the terminal block.
◆
Select the appropriate power cable (Refer to the table above).
Pay attention to the diameter of the connection terminal of the cable, it should be greater than or
equal to that of the connection poles.