KE 4256-3230 Keatec T Series UPS 10-40K 380Vac Users Guide English 20170126 This manual is for qualified personnel only.
Page 28
Maintenance
: Press + OFF key to enter maintenance and display a password window,
press change the number and press OFF to select the value,
the password is “1121”.
Maintenance-System
: press OFF key to enter item and confirm value, press change value.
Operating mode : Normal, Parallel, ECO
V_Output Grade : 220/230/240
F_Output Grade : 50 and 60
F_mode : CVCF and Non-CVCF
Test type : 10s, 10min and EOD
Test Cycle : 1~30 days
Equipment ID : Device address is 1~15, it is the MODBUS device address used for RS232
& RS485 communication ports.
①
Press to set the address 1~15. When
battery temperature sensor is open,
choose 1~10 & 13~15; If it’s parallel
mode and device address <= parallel quantity, device address= parallel ID.
②
Press “ON” to exit the device address setting and save the device
address setting value and parallel ID setting. (Note: Under single UPS mode,
until this device address setting save and exit, single UPS setting is done.)