Temp. Sensor SW : ON or OFF. OFF means turn off the sensor switch, ON means turn on
the sensor switch, send query command to sensor with address 11,12
every second.
Maintenance-Bypass
: press OFF key to enter item and confirm value, press change value.
Upper Limit : 5%, 10%, 15%, 20%, 25%
Lower Limit : -10%, -20%, -30%, -45%
F_Range : 1%, 2%, 4%, 5%, 10%
Maintenance-Battery
: press OFF key to enter item and confirm value, press change value.
Number : 16/18/20 PCS Total (Note: there are 8/9/10pcs for each
“+” string and “-“ string)
Capacity : 7~2000Ah
Boost charge : Enable or disable
Group : 1~8
V-Boost : 2.30~2.40, step is 0.01V
V-Float : 2.20~2.29, step is 0.01V
V-EOD :1.75V or 1.80V