KE2 Evap
OEM
Quick Start Guide
Q.1.45 May 2019
Page 6
Menus and Parameters
ADVANCED Setpoints Menu
Basic (Remote) Display KE2 Combo Display
Min
Max
Default Description
Abbreviation
Scrolling Text
tS
tS
ROOM TEMP
-50.0 0F
90.0 0F
0.0 0F
Room Temp Setpoint - Walk-in room temp to be maintained
rFG
rF
REFRIgERANT
N/A
N/A
R-404A
Type of refrigerant used: See table on page 8.
dtY
dtY
DEFROST TyPE
N/A
N/A
Electric
Type of Defrost for Evap: ELE for Electric/ Ai for off time/ HGn for hot gas w/
comp on/ HGF for hot gas w/comp off
Edt
Edt
VALVE TyPE
N/A
N/A
Mechanical
Type of valve used on system: mechanical, pre-configured electric, custom
EEV configuration
ind
ind
DEFROST MODE
N/A
N/A
Demand
Mode to initiate a defrost: dnd-demand; SCH-Schedule; rnt-comp run time
dPd
dPd
DEFROSTS / DAy
0
8
5
Defrosts per day - If DEFROST MODE = SCH: Number of evenly spaced
defrosts per day the controller will initiate.
dtP
dtP
DEFROST TERM TEMP 35.0 0F
90.0 0F
50.0 0F
The temperature the coil sensor(s) must exceed in order to terminate de-
frost. The controller’s defrost mode is complete at this point.
dEF
dEF
DEFROST
PARAMETER
0
90
30
if DEFROST MODE = DEMAND: Coefficient to KE2 Defrost algorithm
dtL
dtL
MAX DEFROST TIME
0 min
90 min
45 min
If DEFROST MODE = SCH: The maximum amount of time the defrost relay
will be energized. (Not available if DEFROST MODE = DEMAND)
drn
drn
DRAIN TIME
0 min
15 min
2 min
Time to be in drain mode (drip time)
rFt
rFt
REFRIg FAN TyPE
Manage/Cycle,
Permanent, On with
Compressor, Title 24
On with
Compressor
Manage/CYC - manage fans during refrig cycle; Permanent/PEr - fans on
permanently during refrigeration cycle; On with Compressor/FoC - manage
fans in OFF, then ON in refrigeration; Title 24/t24 - Cycle fans based on Title
24 regulations.
FoC
FOC
FANS ON COMP
—
—
—
Manage fans in OFF, then ON in refrigeration
PEr
PEr
FANS PERMANENT
—
—
—
Fans on permanently during refrigeration cycle
CYC
CYC
CyCLE
—
—
—
Cycle (Managed) manage fans during refrig cycle
t24
t24
TITLE 24
—
—
—
Cycle fans based on compliance with California Title 24 regulations
Stt
Stt
SUPERhEAT
5.0 F0
30.0 F0
8.0 F0
Target superheat value. Only applies when non-mechanical valve selected.
LPt
LPt
LOW PRESSURE CUT
OUT TIME
0 min
15 min
0 min
Only applies when non-mechanical valve selected; 0=Disabled
LPC
LPC
LOW PRESSURE CUT
OUT
-5.0 psig
138.0 psig 8.0 psig
Displays when LOW PRESSURE CUTOUT TIME (LPt) is greater than zero.
And,only applies if non-mechanical valve is selected
LPd
LPd
PRESS DIFF FOR
LPCO
1.0 psig
20.0 psig
15.0 psig
Pressure Differential for LPCO - Displays when LOW PRESSURE CUTOUT
TIME (LPt) is greater than zero. And, only applies if non-mechanical valve is
selected
rnt
rnt
COMP RUN TIME
0 hrs
24 hrs
6 hrs
Compressor Run Time - When rnt selected, number of hours of cooling
before starting defrost
Htn
Htn
ELECTRIC DEFROST
MODE
N/A
N/A
Pulse
If DEFROST TYPE = ELE: Whether to leave the defrost relay energized during
the defrost cycle or to utilize advanced defrost algorithm. PUL = Pulse, Prn
= Permanent
HAo
HAo
hIgh TEMP ALARM
OFFSET
0 F0
99.9 F0
10.0 F0
Number of degrees above ROOM TEMP for a HIGH TEMP ALARM condition.
HAd
HAd
hIgh TEMP ALARM
DELAy
0 min
120 min
60 min
Minutes the room temperature must remain above ROOM TEMP + HIGH
TEMP ALARM OFFSET before issuing a HIGH TEMP ALARM
LAo
LAo
LOW TEMP ALARM
OFFSET
0 F0
20.0 F0
4.0 F0
Number of degrees below ROOM TEMP for a LOW TEMP ALARM condition.
LAd
LAd
LOW TEMP ALARM
DELAy
0 min
30 min
10 min
Minutes the room temp must remain below ROOM TEMP-LOWTEMP ALARM
OFFSET before issuing a LOW TEMP ALARM
dAd
dAd
DOOR ALARM DELAy 0 min
180 min
30 min
If AU IN (1, 2 and/or 3) MODE = dor The amount of time, in minutes, before
an alarm condition is initiated, if door is open & room temperature is 5
degrees above ROOM TEMP + AIR TEMP DIFF
AU1
AU1
AUX IN 1 MODE
N/A
N/A
Disabled
See Auxiliary Input Modes table
A1A
A1A
AUX IN 1 STATE
N/A
N/A
Closed
oPn= active if input is an open / CLo=active if input is shorted
AU2
AU2
AUX IN 2 MODE
N/A
N/A
Disabled
See Auxiliary Input Modes table
A2A
A2A
AUX IN 2 STATE
N/A
N/A
Closed
oPn= active if input is an open / CLo=active if input is shorted
AU3
AU3
AUX IN 3 MODE
N/A
N/A
Sys Off
See Auxiliary Input Modes table
A3A
A3A
AUX IN 3 STATE
N/A
N/A
Closed
oPn= active if input is an open / CLo=active if input is shorted
tS2
tS2
ROOM TEMP
-50.0 0F
90.0 0F
-50.0 0F
If AU IN (1, 2 and/or 3) MODE = (t2n) 2ND ROOM TEMP: This value becomes
the ROOM TEMP setpoint when the digital input is active
Unt
Unt
TEMP UNITS
N/A
N/A
Fahrenheit
Units for temperature’s display in 0F or 0C; FAH = Fahrenheit, CEL = Celsius
BASIC Setpoints Menu
Basic (Remote) Display KE2 Combo Display
Min
Max
Default Description
Abbreviation
Scrolling Text
tS
tS
ROOM TEMP
-50.0 0F
90.0 0F
0.0 0F
Room Temp Setpoint - Walk-in freezer or cooler room temp to be maintained
rFG
rF
REFRIgERANT
N/A
N/A
R-404A
Type of refrigerant used: see table below
dtY
dtY
DEFROST TyPE
N/A
N/A
Electric
Type of Defrost for Evap: ELE for Electric/ Ai for off time/ HGn for hot gas w/
comp on/ HGF for hot gas w/comp off