© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.1.45 May 2019
Page 7
KE2 Evap
OEM
Quick Start Guide
ADVANCED Setpoints Menu (continued)
Basic (Remote) Display KE2 Combo Display
Min
Max
Default Description
Abbreviation
Scrolling Text
EdF
EdF
EXTREME TEMP DIFF
0 0F
99.9 0F
20.0 0F
ADVANCED TOPIC: Call KE2 Therm for assistance
CLA
CLA
CLEAR ALARMS
N/A
N/A
Press and hold to clear all active alarms
diA
diA
DIAgNOSTICS MODE N/A
N/A
Energizes each relay individually for 60 seconds: fan relay, defrost relay,
compressor relay
FAC
FAC
FACTORy RESET
N/A
N/A
Press and hold to reset the controller to the factory default setpoints
PAS
PAS
WEB PASSWORD
RESET
N/A
N/A
Press and hold to reset the web password to the factory default
SA
SA
SMART ACCESS
N/A
N/A
Disabled
Turn KE2 Smart Access on or off: EnA to enable smart access / diS to disable
KE2 Smart Access
dHC
dHC
DhCP
N/A
N/A
Enabled
Turn DHCP mode on or off: EnA to enable DHCP mode / diS to disable DHCP
mode
Not Available
on Basic Display
MOTOR TyPE
Unipolar or Bipolar
Unipolar
Unipolar if unipolar stepper used, Bipolar if bipolar stepper used
MOTOR STEP RATE
30
400
40
Motor Step rate for custom valve. Not available on Basic Display
MAX VALVE STEPS
200
6400
500
Full stroke steps for custom valve. Not available on Basic Display
MAX OPERATINg
PRES
10.0 psi
150.0 psi** 150.0 psi**
**Max operating pressure. Max is 300 when R-410A selected and 500 when
R-744 selected
FAN SPEED
-100.0%
100.0%
0.0%
Fan speed %. Not available on Basic Display
MIN COMP RUN TIME 0 min
15 min
2 min
Minimum Compressor Run Time. Not available on Basic Display
MIN COMP OFF TIME 0 min
15 min
5 min
Minimum Compressor Off Time. Not available on Basic Display
REFRIg FAN MODE
Manage, Permanent,
ON with Compressor,
Title 24
ON with
compressor
Managed = manage fans during refrig cycle; Permanent = fans ON perma-
nent during refrig cycle; On with Compressor = manage fans in OFF then
ON in refrig; Title 24 = cycle fans based on Title 24 regulations
1ST DEFROST DELAy 0 min
240 min
120 min
First Defrost Delay. Not available on Basic Display
DEFROST FAN STATE
ON or OFF
OFF(E)/ON(A) OFF = fans off during defrost; ON = fans ON during defrost
FAN DELAy TEMP
-40.0 0F
35.0 0F
20.0 0F
Fan delay temp. Not available on Basic Display
MAX FAN DELAy
TIME
0 min
20 min
2 min
Max fan delay time. Not available on Basic Display
PUMP DOWN TIME
0 min
90 min
0 min
Minimum amount of time between de-energizing the liquid line solenoid/
compressor relay and energizing the defrost relay.
MULTI AIR TEMP CTRL Warmest or Average
Warmest Air Warmest air = use the warmest air temp from bonded controls; Average air
= use the average air temp from bonded controls
MULTI EVAP COOL
Synchronized or
Independent
Synchronized
Synchronized = synchronize bonded controller in refrigeration mode;
Independent = bonded controllers control temperature independently in
refrigeration mode.
MULTI EVAP DEFROST Synchronized or
Independent
Synchronized Synchronized = synchronize bonded controller in defrost mode; Indepen-
dent = bonded controllers defrost independently
MULTI EVAP SENSOR Shared or Unshared
Shared
Shared = share sensor readings from bonded controllers; Unshared = use
local sensor readings only
SUCT PRES OFFSET
-5.0 F0
5.0 F0
0.0 F0
An offset added or subtracted from the suction line pressure transducer
reading, if needed
SUCT TEMP OFFSET
-5.0 F0
5.0 F0
0.0 F0
An offset added or subtracted from the suction temperature sensor reading,
if needed
COIL TEMP OFFSET
-5.0 F0
5.0 F0
0.0 F0
An offset added or subtracted from the coil temperature sensor reading, if
needed
AIR TEMP OFFSET
-5.0 F0
5.0 F0
0.0 F0
An offset added or subtracted from the room temperature sensor reading,
if needed
AUX 1 OFFSET
-5.0 F0
5.0 F0
0.0 F0
When Aux1, Aux2, or Aux 3 are used as a temperature sensor, an offset is
added or subtracted from the reading.
AUX 2 OFFSET
-5.0 F0
5.0 F0
0.0 F0
AUX 3 OFFSET
-5.0 F0
5.0 F0
0.0 F0
PROPORTIONAL
0
255
3
A coefficient to the valve control algorithm that increases valve responsive-
ness as the value increases
INTEgRAL
0
255
5
A coefficient to the valve control algorithm that increases valve responsive-
ness as the value increases
DERIVATIVE
0
255
3
Should not be adjusted unless instructed by KE2 Therm
AIR TEMP DIFF
0.1
5.0
1.0 F0
The number of degrees above ROOM TEMP before the controller will go into
REFRIGERATION mode
DEFROST FAN STATE Off
Off
On
Fan state during the defrost cycle
MULTI AIR TEMP
CTRL
Average
Warmest
Warmest
Select control method to use with multiple room temperature sensors
MULTI EVAP COOL
Sync
Indepen-
dent
Sync
Select type of multi evaporator control - options are synchronous or
independent
MULTI EVAP DE-
FROST
Sync
Indepen-
dent
Sync
Select whether to have all bonded controllers initiate defrost mode at the
same time or independently.
MULTI EVAP SENSOR Shared
Not Shared Not Shared
Select whether or not to share room temperature, coil temperature and suc-
tion pressure sensor data with bonded controllers.