Function test:
After all values have been programmed, a function test should be performed. To do so, the controller has to be
taken off the voltage supply for a few seconds.
After connecting it to the voltage supply, the controller has to start automatically. When reading out the CosPhi
voltage in the start menu immediately after switching on, CosPhi should be inductive. After approx. 60 seconds,
the controller starts to switch on the individual capacitor stages, until the facility is compensated.
The CosPhi, which can be read out in the start menu, should have risen in comparison with former
values, or it should rise when switching on additional stages. If the compensation facility is set up
correctly, the controller should compensate the set target CosPhi after a certain period of time.