Operating instructions
multicomp
Version 1.00
Page 25 of 29
ED
EBD
A
014
4
/ 05
11
-1
GB
10
Setting range of the parameters configurable
Primary voltage
1 V to 39999 V Ph-Ph
Secondary voltage
1 V to 999 V Ph-Ph
Primary current
1 A to 39999 A
Secondary current
1 and 5 A
Rot.field U
L1N, L2N, L3N, L12, L23, L31
Rot.field I
L1, L2, L3, -L1, -L2, -L3
Consumption target CosPhi
ind. 0.80 to cap. 0.80
Recovery target CosPhi
ind. 1.0 (cannot be set)
FTS Alarm CosPhi
ind. 0.70 to 1.0
Attenuation coefficient current
0 to 9
Attenuation coefficient voltage
0 to 9
Attenuation coefficient Qmiss
0 to 9
Idle time
0 to 300 sec.
Alarm relay time
0 to 3000 sec.
Hysteresis connection
70 to 150 %
Hysteresis disconnection
70 to 150 %
Switching interval
0 to 10 sec.
Limit switching cycles
0 to 999999
Stage power
0 to 999.9 kvar
Discharge time
0, 3, 30, 60, 90, 300, 600, 900 sec.
Stage switching mode
= Automatic, manual off, manual on
Stage power monitoring
Deactivatable
Harmonics monitoring
Deactivatable (0%)
THD limit
0 to 10%
Scanning frequency
Automatic, fixed 50 Hz, fixed 60 Hz
Password
No password (9999, meaning all functions are accessible)
Display language
German, English, French or Spanish
Contrast settings
0 to 10
Error message dialog:
Missing measurement voltage
The settings Message or alarm relay /
Missing measurement current
Message and error relay / Off
Missing stage power
is identical for all errors!
Facility too small
THD too high
Switching cycle limit exceeded
Light load operation
Error message dialog after reset:
Missing measurement voltage
Alarm relay
Missing current
Message
Missing stage power
Alarm relay
FTS (Facility Too Small)
Message and alarm relay
THD too high
Alarm relay
Switching cycle limit exceeded
Alarm relay
Light load operation
Off