V2.01
25360_EDEBD
A0280-2320-1_EN
11
Control and display panel
General notes on operating the sensor buttons:
U
button
Start configuration and reset input
V
button
Change values during configuration
W
button
Navigate through submenus
X
butto
Navigate through main menus and save button during
configuration
Button combinations:
U
and
V
buttons
Delete accumulated values and reset the system
Default controller settings after reset:
Consumption target cos phi: 0.95 inductive
Recovery target cos phi:
1.00 (cannot be changed)
Alarm cos phi:
0.92 inductive
Main transformer current:
Primary current 1000 A
Secondary current 5 A
Measuring voltage:
Primary voltage 400 V Ph-Ph (corresponds to 230V Ph-N)
Secondary voltage 400 V Ph-Ph (corresponds to 230V Ph-N)
Rot. field U:
L1-N
Rot. field I:
L1
Current attenuation coefficient: 0
Voltage attenuation coefficient: 0
Attenuation coefficient Q
miss
: 0
Alarm delay:
20 minutes (1200 s)
Idle time:
30 ms
Switching interval:
50 ms
Hysteresis connection:
100% of lowest stage power
Hysteresis switch-off:
100% of lowest stage power
Switching performance Priority Operation cycles, 24hours Switching off
Operating cycle count:
active
Stage switching mode:
Automatic
Sampling rate:
Automatic