Description of the display window
Switching interval (default setting 50 ms, setting range 50 to 9999 ms):
This value defines the time the controller is idle between two switching operations.
Alarm cos phi (default setting ind. 0.92, setting range ind. 0.70 to 1.0):
This value is connected to the message
PFC too small
. If this value is not reached
after the alarm delay has elapsed, despite all stages being switched on, the message
PFC too small
is displayed.
Attenuation Q
miss
(default settings 2, setting range 0 to 9):
This value defines the attenuation of the display and control behavior to prevent rapid
parameter changes if there is no compensation power.
Attenuation U (default setting 0, setting range 0 to 9):
This value defines the display attenuation to prevent rapid parameter changes of the
measuring voltage.
Attenuation I (default setting 2, setting range 0 to 9):
This value defines the display attenuation to prevent rapid parameter changes of the
measuring current.