Control and display panel
The controls in the compensation systems are preset.
The following parameters need to be checked or set:
Target cos phi in accordance with the electricity supplier regulations
(for kVA tariff cos phi = 1)
Primary current and secondary current in accordance with input current transformer.
Voltage transformer ratio, if required
NOTE
Upon delivery, the bus protocol is set to:
Modbus RTU, baud rate 38400, parity even
This setting can only be changed manually on the device.
Performing a "Reset to default settings" has no effect on changed settings.