Low voltage current transformers, multict KBR
6. Error Recovery
e.g. unexpected or wrong values, reverse performance
Check the settings of the measuring device according to its instruction manual.
C heck whether the current transformer is mounted on the intended conductor in the
direction of the energy fl ow.
Check whether the current transformer is closed properly.
Check the power requirements of the cables and measuring devices connected to the
current transformer. This must not exceed the rated power of the current transformer.
(See rating plate.)
Should the aforementioned points not solve the problem: Check for dust or other
contamination between both parts of the core. If so, gently clean the surfaces with a
lint-free cloth.
Avoid hand contact (sweat)!
7. Technical data (for exact data, see rating plate)
7.1. Technical data (general)
Input
Primary rated current I
pr
:
see table in 7.2.
Thermal rated uninterrupted current I
cth
:
1.2 x I
pr
KBR 18, 32, 44
1.0 x I
pr
other types
Thermal rated short-time current I
th
:
60 x I
pr
/1s
Rated surge current l
dyn
:
2.5 x I
th
Rated frequency f
R
:
50 … 60 Hz
Output
Secondary rated current I
sr
:
see table in 7.2.
Optional voltage output
KBR 18, KBR 32, KBR 44:
0…0.333V AC
External load min.100 kΩ
Accuracy class:
0.5 … 3
Rated power S
r
:
0.3 … 5 VA
Overcurrent limit factor FS:
FS5 or FS10