53
11.3 Erp imformation
KMF-180 DTR6
Cooling mode:
Information requirements for air-to-air conditioners
Model(s):
KMF-180 DTR6
Test matching indoor units form, ducted: 4×
Outdoor side heat exchanger of air conditioner: air
Indoor side heat exchanger of air conditioner: air
Type: compressor driven
Driver of compressor: electric motor
Rated cooling capacity
Seasonal space cooling
energy efficiency
Item
Symbol
P
rated,c
17.50
Value
Unit
Item
Symbol
Value
Unit
kW
Declared cooling capacity for part load at given outdoor
temperatures T
j
and indoor 27/19°C
(
dry/wet bulb
)
η
s,c
281.0
%
Declared energy efficiency ratio or gas utilisation efficiency
/auxiliary energy factor for part load at given outdoor
temperatures T
j
T
j
=+35°C
T
j
=+30°C
T
j
=+25°C
T
j
=+20°C
Off mode
Thermosat-off mode
Crankcase heater mode
Standby mode
P
CK
P
SB
P
dc
P
dc
P
dc
P
dc
17.50
12.63
8.15
4.41
kW
kW
kW
kW
kW
kW
kW
kW
T
j
=+35°C
T
j
=+30°C
T
j
=+25°C
T
j
=+20°C
EER
d
EER
d
EER
d
EER
d
2.71
4.70
8.68
15.81
--
--
--
--
Degradation
co-efficient for air
conditioners(*)
C
dc
0.25
--
Power consumption in modes other than "active mode"
P
OFF
P
TO
0.005
0.002
0.002
0.005
Other items
Capacity control
variable
For air-to-air air conditioner:
air flow rate, outdoor
measured
Sound power
level, outdoor
L
WA
73
dB
GWP of the refrigerant
675
kg CO
2 eq
(100years)
5500
m
3
/h
--
Contact details
(*)If C
dc
is not determined by measurement, then the default degradation coefficient of heat pumps shall be 0.25.
Where information relates to multi-split air conditioners, the test result and performance data may be obtained on the basis
of performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.